Explore! How to soft start the high-power compressor? This approach is worth recommending
In the circuit design of the compressor, a low-power motor can use the direct start mode, because the instantaneous current is small, and generally it will not cause an impact on the power grid. If it is a relatively high-power motor, the instantaneous current at startup is 4 to 7 times the normal operating current. A large instantaneous current will impact the entire power supply and distribution system, and in severe cases may cause high and low voltage circuit breaks in the power distribution room. The switch tripped, which caused a company-wide power outage, which affected normal production and life. For this reason, how to reduce the starting current for high-power compressors is a problem that must be paid attention to in the compressor circuit design.
1. Distinguishing point of high-power compressor motor
Generally, the compressor power is allowed to start directly below 7.5kW, but for large compressors, it is not allowed to start directly. If the rated current is 100A, then the instantaneous current can reach hundreds of amperes at the moment of startup. Such a large current has a very large impact on the grid and will affect the normal operation of other loads on the same grid. This situation can often be seen .
Calculation of motor load rotation power
2. Definition of soft start of high-power compressor motor
When considering this issue, let us first understand what is AC motor soft start? By adding additional devices, the stress impact on the motor itself and the power grid is reduced, so that the starting process of the motor from zero speed up to the rated speed is more stable. This process is called motor soft start. This additional device is called a motor soft starter. Note: The motors mentioned here refer to AC motors.
Soft start is relative to direct start. From a certain perspective, if the impact of direct starting on the motor and load is ignored, any motor can be started directly as long as the grid capacity is large enough. Then why use a soft starter?
1. The grid capacity is not unlimited
When the motor is started directly, the starting current is 5-7 times the normal operation. This current acts on the impedance of the limited capacity power grid and will produce a voltage drop. The voltage drop of the power grid to a certain extent will affect the normal operation of other equipment on the power grid. To solve this problem, one way is to increase the grid capacity, but the increase of the grid capacity requires the increase of transformer capacity and line capacity, which greatly increases the cost. At the end of the start, when the motor is running normally, the capacity of the power grid is not fully utilized, and the increased no-load loss of the transformer also greatly increases, which wastes a lot of electrical energy. Therefore, when the transformation project needs to expand the power grid, and the original design power grid capacity cannot be changed, or the new project takes into account the cost of increasing the power grid capacity, another method must be adopted, that is, the installation of a soft starter.
2. The harm caused by excessive starting current and soft starting torque
The direct starting current of ordinary asynchronous motors can reach 5-7 times of the rated current, and the starting torque can reach more than 1.25 times of the rated torque. It can be started directly when the grid conditions (the grid voltage drop when the motor starts is less than 10%) and the process conditions (the starting torque is satisfied) allow. However, excessive starting current will cause great harm to the motor and the power grid.
When the starting current of the motor reaches 6-7 times of the rated current, the heat generated by the coil is 36-49 times that of the motor during normal operation. Too high temperature, too fast heating speed, too large temperature gradient and electromagnetic force will produce great destructive force, shorten the stator coil and rotor copper bar (especially the rotor often uses the skin effect phenomenon to reduce the starting current, When the rotor copper bar is started, the surface temperature reaches 350℃ or more) the service life.
Explanation: What is the skin effect? When there is alternating current or alternating electromagnetic field in the conductor, the current distribution inside the conductor is not uniform, and the current is concentrated in the "skin" part of the conductor, that is to say, the current is concentrated in the thin layer on the outer surface of the conductor. The closer to the surface of the conductor, the greater the current density, and the actual current inside the wire is smaller. As a result, the resistance of the conductor increases, and its power loss also increases. This phenomenon is called the skin effect, so from the perspective of protecting the motor, a soft starter should also be used.
3. The impact of excessive starting current on production and life
The light bulb will dim the moment a large load is started. We sometimes encounter this situation at home. For example, when the TV is turned on, the light bulb will sometimes dim suddenly. Similarly, the starting current of the load is too large, which is extremely disadvantageous to the insulation of the motor windings. Therefore, soft start is generally required for large compressors. The voltage of the soft starter to the motor gradually changes from 0 to the rated voltage. Its starting process is smoother, the starting effect is better, the impact on the grid and the damage to the windings are also minimal, which is better than the autotransformer step-down start.
3. Design principles of soft-start circuit for high-power compressors
1. Load capacity design of soft starter
The load capacity of the soft starter mainly refers to the overload capacity. Due to the difference of the actual working system, the actual loading situation of the soft starter is also different. For example, in the starting process, it will generally bear 2-4 times the rated current, and the time is usually within 60S. Therefore, for the long-term work system, the soft starter actually belongs to the short-term overload work during the starting process; and for the repeated short In terms of the hourly duty system, the soft starter belongs to long-time overload work during the starting process. Since the heat capacity of power semiconductor devices (thyristors) is very small, the overload capacity of the device is mainly determined by the overload capacity of the power conductor device and the heat dissipation capacity of the soft starter.
The overload capacity of the soft starter is generally designed according to the following principles:
(1) The overload that lasts for more than 15 minutes is generally designed according to the continuous load condition.
(2) For overloads that last less than 15 minutes, calculate the device's overload capacity and select the device by calculating the junction temperature of the device according to the transient thermal impedance curve of the thyristor device.
Therefore, when choosing a soft starter, you should refer to its related instructions to clarify the applicable rated work system and applicable standards of the product to determine the actual load capacity of the product.
Note: Generally speaking, the larger the thyristor capacity, the larger the radiator size, and the larger the cooling fan, the stronger the load capacity of the corresponding soft starter. Of course, the volume and cost of the corresponding equipment are higher. For power electronic equipment, under the same capacity, it is by no means that the smaller the size, the better. This point should be paid attention to.
2. Understanding of some errors in the application of soft starter
(1) It is believed that whether the motor can start successfully is related to the performance of the soft starter, and a good brand or even a foreign brand should be selected under heavier load;
(2) When the motor cannot start the load, it is considered that the capacity of the soft starter is insufficient, and the capacity of the soft starter should be increased;
(3) It is considered that a certain starting method is particularly suitable for "heavy load" starting;
(4) It is believed that the smaller the starting current is, the better the performance of the soft starter that reduces the voltage of the power grid.