ABC overhead Line Wire

Model
Nature of the Manufacturer
Other
Product Category
LV ABC Cable
Place of Origin
City, Province
Overview
ABC overhead Line Wire is used primarily for overhead secondary distribution lines. It is not an electrically insulated conductor and is treated as bare conductor when installed.
Product Details

Applications of ABC overhead Line Wire

Covered Line Wire is used primarily for overhead secondary distribution lines. It is not an electrically insulated conductor and is treated as bare conductor when installed.

Construction of ABC overhead Line Wire

Conductors are aluminum alloy 1350-H19, 6201-181, or ACSR conductors, concentrically stranded and covered for weather proofing with polyethylene, high density polyethylene (HD) or crosslinked polyethylene (XLPE).

Standards of ABC overhead Line Wire

  • ASTM B-230 - Aluminum 1350-H19 Wire for Electrical Purposes.

  • ASTM B-231 - Concentric-Lay-Stranded Aluminum Conductors, Coated-Steel Reinforced (ACSR).

  • ASTM B-1248 - Polyethylene Plastics Molding and Extrusion Materials.

  • ASTM C-8.35 - Specifications for Weather-Resistant Polyethylene-Covered Wire and Cable.

  • ICEAS-61-402

  • NEMA PUB NO. WC 5-1973 - Standards Publication Thermoplastic insulated Wire and Cable for the Transmission and Distribution of Electrical Energy.

Notes

  • The code words as given apply to conventional polyethylene line wire.

  • For 6201 aluminum conductors diameter equivalent to ACSR construction or 1350 aluminum equivalent.

  • Ampacity ratings based on 75 ºC conductor temperature, 25 ºC ambient temperature elevation - sea level. Emissivity 0.91 coefficient of absorption 0.95. Thermal resistivity of covering -3 ºC-Cm2/Watt-CM. Wind speed 2ft/sec in sun.

  • To determine correct ampacity by conductor size, please consult the National Electric Code, latest edition.