1 KV PVC Insulated Cable

Model
Nature of the Manufacturer
Other
Product Category
LV ABC Cable
Place of Origin
City, Province
Overview
The aerial Bundled cables designed for overhead distribution lines have an insulated neutral messenger made of AAAC, which the insulated aluminium phase conductor are helically wound over it. Cables are rated at 0.6/1(1.2)kV and conform to IEC60502.
Product Details

1KV Aerial Bundled Cables Aluminium Phase Conductor

PVC insulated overhead cable (2)

Application of 1 KV PVC Insulated Cable

ABC (Aerial Bundled Cables or Aerial Bundled Conductors) are several phase conductors insulated and tightly bundled together with bare neutral conductor for use in overhead power lines.

Construction of 1 KV PVC Insulated Cable

1. Conductor:

a) Phase - The phase conductor shall be of H68 Condition aluminium conductor and compacted circular stranded.

b) Neutral or messenger - The Neutral or messenger conductor shall be of aluminium alloy conductor and compacted circular stranded c)

Street Lighting- The street lighting conductors shall be of H68 condition aluminium conductor and compacted circular stranded..

2. Insulation:

The phase, neutral conductors shall be extruded with polyethylene(PE) as insulation.

0.6/1(1.2)kV AL/XLPE(PE) Insulated

Aerial Bundled Cables with Street Lighting Conductor

PVC insulated overhead cable (3)

3 Phase conductors + 1 Messenger conductor + 1 Street lighting conductor

Description of 1 KV PVC Insulated Cable

The aerial Bundled cables designed for overhead distribution lines have an insulated neutral messenger made of AAAC, which the insulated aluminium phase conductor are helically wound over it.

Cables are rated at 0.6/1(1.2)kV and conform to IEC60502.

Phase conductor










Nominal cross-sectional area

mm²

25

35

50

70

95

120

150

185

Number of cores


3

3

3

3

3

3

3

3

Minimum number of wires


6

6

6

12

15

15

30

30

Nominal insulation thickness

mm

1.2

1.2

1.4

1.4

1.6

1.6

1.8

2.0

Diameter of insulated core

mm

8.5

9.5

11.2

13.0

15.1

16.6

18.4

20.6

Max. DC resistance at 20℃

ohm/km

1.20

0.868

0.641

0.443

0.320

0.253

0.206

0.164

Current rating at still wind, ambient

A

84

104

129

167

209

246

283

332

temperature=30℃










Conductor temperature=75℃










Messenger conductor










Nominal cross-sectional area

mm²

25

25

35

50

70

70

95

120

Minimum number of wires


6

6

6

6

12

12

15

15

Nominal insulation thickness

mm

1.2

1.2

1.2

1.4

1.4

1.4

1.6

1.6

Diameter of insulated core

mm

8.5

8.5

9.5

11.2

13.1

13.1

15.1

16.6

Max. DC resistance at 20℃

ohm/km

1.312

1.312

0.943

0.693

0.469

0.469

0.349

0.273

Calculated breaking load

kN

6.4

6.4

8.9

12.1

18.0

18.0

24.2

30.8

Street lighting conductor










Nominal cross-sectional area

mm²

25

25

35

50

70

70

95

120

Minimum number of wires


6

6

6

6

12

12

15

15

Nominal insulation thickness

mm

1.2

1.2

1.2

1.4

1.4

1.4

1.6

1.6

Diameter of insulated core

mm

8.5

8.5

9.5

11.2

13.1

13.1

15.1

16.6

Max. DC resistance at 20℃

ohm/km

1.312

1.312

0.943

0.693

0.469

0.469

0.349

0.273

Completed cable










Approx. overall diameter

mm

23.2

25.6

30.0

34.9

40.6

44.1

49.2

54.9

Approx. weight of cable

kg/km

470

560

740

980

1330

1580

1940

2410

Packing length

m/drum

1000

1000

1000

1000

500

500

500

500