BOS high-voltage big capacity shore power supplymainly adopt the input transformer, power units and other components connectedto each other. The shore power structure is with multiple units in series, theoutput parts with multi-level phase-shifted PWM technology, which make thepower supply be high reliability, small size , Greatly reducing themanufacturing materials, light weight, easy to move; automatically match theoptimal technical parameters, reducing the wiring inductance; Compared with thetraditional d......
1.Rated input voltage: input power for the three-phase10KV / 50HZ industrial power supply. (AC voltage allowable fluctuation range ±10%)
2. Rated output voltage: the output voltage according touser needs, to provide a variety of voltage levels, 6KV / 6.6KV / 10KV. In thiscase,
3. Rated output frequency: 60HZ / 50HZ (can bearbitrarily converted)
4.Output frequency accuracy and stability: output frequencyerror ≤ 0.01Hz; stability <0.01% (0 ~ 99% load change, the frequencyunchanged)
5. Output voltage regulation rate: static <3%;dynamic <5%
6.50% load sudden increase / decrease when the outputvoltage instantaneous change: <5%, and 0.5 seconds to restore to the ratedoutput voltage
7. frequency power overload capacity: 120% 2 minutes;150% for three seconds; 180% immediate protection
8. Output voltage waveform Total harmonic distortion:THD ≤ 1.2 ~ 2.8%;
1 | Standard | GB/T 12668-2012 |
2 | Installation Place | In room |
3 | Tech program | Multistage unit series, AC-DC-AC, high voltage source type |
4 | Requirement for the motor | AC asynchronous motor |
5 | Rated input voltage range | ±10% |
6 | Systerm Input voltage | 6 kV /10 kV |
7 | System output voltage | 0-6 kV /10 kV |
8 | Inverte side Max output voltage | 6 kV /10 kV |
9 | Rated Capacity | 250-4000KW/315-5000KVA |
10 | Rated Input frequency range | 50HZ/±10% |
11 | Grid voltage wave sensibility | -15%+15% full load;35%load shedding |
12 | Efficiency | ≥96% |
13 | THD | ≤2% |
14 | Reliability index | 50000 H |
15 | Input side PF | ≥0.96 |
16 | Control type | PWM |
17 | Control power source | AC 380V |
18 | Rectifier form &component parameters | 1800V 3P No controlled rectifier bridge |
19 | Inverter form and component parameters | 1700V IGBT |
20 | Noise | <65dB |
21 | Cooling type | Force air |
22 | Overheating protection | High temperature alarm , overtemperature trip |
23 | Overload | 120%2M;150% 3S;180% immediately |
24 | Frequency converter loss | <2% kW |
25 | Total loss | <4% kW |
26 | Standard control connection | hardwired connection |
27 | Analog input specifications and quantity | 1×4~20mA open end |
28 | Analog output specifications and quantity | 4×4~20mA open end |
29 | Switch input and specification and quantity | 9×500VAC open end |
30 | Switch signal specification and quantity | 12×DC220V/10A open end |
31 | Protection grade | IP30 |
32 | Control interface | Touch Screen |
33 | Language | Chinese or English |
34 | Size | See catalog |