Welcome Customer !

Membership

BEIJING SOLINITY Electrical Co., Ltd
Free Member ·1YRS
,
Other

Main Products: 电气设备

Xwboo>Products

PIM620AC-F96 Three-phase Multi-function Monitoring Meter

Model
Nature of the Manufacturer
Other
Product Category
Three-phase Multimeters
Place of Origin
City, Province
Overview
Measure three phase / wire voltage, zero sequence voltage, degree of unbalance three-phase voltage unbalance, phase current, frequency, zero-sequence current, three-phase current imbalance, active power, reactive power, power factor Support 31 times harmonic voltage current containing rate statistics, voltage current total harmonic distortion rate Standard CT, PT or voltage direct input ,which can be used for a variety of connecting wire. ......
Product Details

●Measure three phase / wire voltage, zero sequence voltage, degree of unbalance three-phase voltage unbalance, phase current, frequency, zero-sequence current, three-phase current imbalance, active power, reactive power, power factor
●Support 31 times harmonic voltage current containing rate statistics, voltage current total harmonic distortion rate
●Standard CT, PT or voltage direct input ,which can be used for a variety of connecting wire.
●Electronic energy metering:active electronic energy(kwh) ,reactive energy(kwarh) and bidirectional four quadrant electric energy
●Wide measurement range of AC and DC universal power: AC/DC110V ~ 250V
 
●All instrument parameters can be set through the display panel


Electrical Specification
Accuracy
Current/Voltage
0.2%
Power
0.5%
Electric Energy
Active energy Class 1 (0.5 selected)
 
Input Voltage
 
Nominal Voltage
AC 100V, 380V
Overload
 
 1.2 times rating value( continuous) 2500V/sec( no recurrence)
Input Load
0.1VA max
Input Range
AC 2V~660V
 
Input Current
 
Basic Current
AC 1A, 5A
Overload
 2 times rating value( continuously) 100A/sec(no recurrence)
Input Load
0.1VA Max
Input Range
AC 10A~6A
Input  Frequency
 
Input Range
45Hz~75Hz
Nominal Frequency
50Hz/60Hz
Power
AC/DC
AC/DC 110V~250V
Power Consumption
<3w
Discrete Input (light insulation )
Passive Dry Contact
 
DC power can be provided inside without external power
Relay contact capacity
Relay
5A/250VAC 5A/30VDC
Environmental Rating
Operating Temperature
-20℃~+ 55℃
Storege Temperature
-40℃~+ 85℃
Humidity
≤90%RH
Pollution Class
2 Grade
Elevation
≤4000m
Others
 Used in no corrosive gas
Electromagnetic Compatibility
Power Frequency Voltage Withstand
2.5Kv( Experiments voltage for AC effective Value)
Insulation Resistance
≥500 MΩ
MTBF
≥100000h
Electrostatic Dischage Immunity
 Grade 4
Electrical Fast Transient/Burst Immunity Test
 Grade 4
Surge Immunity Test
Grade 4
Radiation Electromagnetic Field Immunity
Grade 4
 
The term “Accuracy” is given by JJF1001 “Universal Metrological Terms and Definitions”.
It has the same meaning with “precision”

●Energy management system
●Industrial automation
●Substation Automation
●Distribution Network Automation
 
●Intelligent Building


Dimension and Hole size
Meter Model No.
 
Optional function
Optional Function for All
 
Outline96(mm)
Face frame:
96×96
Hole:
91×91
Depth:66
 
PIM620AC-F96
1.one way RS-485communication (C)
1.4DI+C
2.4DI+2DO+C
3.2DI+2DO+K+C
4.4DI+2DO+M+C
5.4DI+2DO+M+A+C
 
2.4DI remote signal input
3.one way electrical pulse output (k)
4.2DO remote control output
5.one way out of limit alarm output.(M)
6.one way DC4DC4~20mA Analog signal output