H/L Voltage Clamp Ammeter

Model
FR1000
Nature of the Manufacturer
Other
Product Category
High Voltage Test Series
Place of Origin
City, Province
Overview
H/L Voltage Clamp Ammeter
Product Details
FR1000 high-low voltage ampere meter is a high-pressure measurement tool. It is composed of a special clamp ammeter with high voltage insulation rod. Inside the clamp ammeter, a mask integrated circuit is used, and an insulating rod is used to measure the current of a high voltage line with insulation sheath below 60 kV or bare wire below 35 kV . When not using the insulation rod, it can also be used as a high-precision low-voltage clamp ammeter, leakage current meter, can accurately split out the current or leakage current of 0.1mA.
It is easy to use and carry. Equipped with telescopic insulation rod, it is easy to carry and use. It uses high-precision CT technology to ensure high-precision, high-reliability, and high-stability for years of uninterrupted testing.
High-voltage clamp current meter also has a peak hold, data retention, data storage and other functions, its special clamp ammeter by pushing or pulling back the insulation rod can easily clamp or split off the measured wire, save time and fast. It can be widely used in substations, power plants, industrial and mining enterprises and testing stations, electrical maintenance departments for current detection and field electrical work. Insulation rods are lightweight, moisture-proof, high-temperature resistant, shock-resistant, anti-bending, high insulation and retractable

Range0.0mA~1200A Auto Range
Resolution0.1mA
Clamp DiameterΦ50mm
Accuracy±2%±5dgt
Sampling SpeedAbout 2 times/second
FunctionHigh-low voltage current measurement
Power SupplyDC6V Alkaline Dry Battery (1.5V AAA X 4)
Test MethodClamp CT, Integral Method
Meter DimensionW/T/H: 87mm×37mmx262mm
LCD Dimension47mm×31mm
Total Weight2.5Kg (including insulation rod and battery.)
Overflow DisplayExceed measurement range overflow function: “OL ” symbol display
Data Storage99 Groups
Data Storage Fullthe symbol “FULL” mark will flash to indicate the memory has been full.
Battery VoltageWhen the battery voltage is below 5.2V, the symbol of battery voltage is low will show
Insulated Rod1m/Section(5 Sections)
Insulation IntensionAC 60KV/rms
Circuit TestInsulation sheath wire test below 60kV line voltage, bare wire test under 35kV (with insulation rod operation)
Work Temperature-10℃~40℃
Storage Temperature-10℃~60℃
Humidity0℃~31℃≤75%, 31℃~40℃≤50%
Suitable for safety regulationsEC1010-1, IEC1010-2-032, Pollution Level 2, CATⅢ(600V) IEC61326 (EMC Standard)

Tester1PC
Insulation Rod1SET(5m)
Meter Bag1PC
Tester (battery) DC6V 7# alkaline battery4 PCS
User’s Manual1SET