Contact Now

High-precision Clamp Current Sens

Model
FR008
Nature of the Manufacturer
Other
Product Category
Current Sensor Series
Place of Origin
City, Province
Overview
High-precision Clamp Current Sens
Product Details
FR008 clamp current sensor is a high-precision AC current convertor. It adopts a clamp-shaped structure. It can be quickly and easily accessed and used. The compact size is easier to carry and use. Applicable to AC current, leakage current, high harmonic current, phase, electric energy, power, power factor and other tests.
FR008 can be used with a variety of measuring instruments, such as: Field calibrator for watt-hour meter, multi-function energy meter, oscillometer, digital multimeter, electrical identification device, cable fault detector, dual-clamp phase volt-ampere meter, three-phase digital phase Volt-ampere meter, etc., can measure and compare a variety of electrical parameters under constant power. Widely used in substations, power plants, industrial and mining enterprises and testing stations, electrical maintenance departments for current detection and field electrical work, etc.

Technical Specification

FeaturesPortable CT clamp structure, safe and convenient to use
Jaw SizeΦ7.5mm
RangeAC 0~30A
ResolutionAC 0.01mA
Accuracy±0.2%FS(50Hz/60Hz; 23 °C±2 °C)
Phase Error≤2°(50Hz/60Hz;23 °C±2°C)
Turn Ratio2500:1 (optional 2000:1; 1000:1)
Reference LoadRL: 0~300mA≤100Ω; 0~3A≤10Ω; 0~30A≤5Ω
DimensionsL/T/H 42mmX 20mmx 137mm
Output Interface3.5mm audio plug
Output Line Length2m
Weight180g
Output MethodCurrent sensing output
External MaterialABS resin, flame retardant rating 94V0
Line Voltage600V AC (insulated wire) 30Vac (bare wire) test
Working Temperature-25°C~55 °C
Insulation Resistance100 MΩ @ 500Vdc
Medium StrengthAC3700V/rms (between iron core and shell)
Current Frequency45Hz~65Hz(measured current frequency)
Frequency Characteristics10Hz~100kHz



Installation Dimensions
  1. Clamp head
  2. direction marker identification (identify the same name when phase detection)
  3. Output leads
  4. Sensor output plug (p3.5mm audio plug)
  5. coil taps