Charge input voltage | AC 220V±10%, 110V±10%, or 380V±10% |
Charge current through the incoming wire of commercial power | About 10A in general, charge automatically by the way of constant voltage and limit current, customize the larger current |
Three phase input phase sequence protection | No output if the sequence of three phase input is wrong,work normally after exchange any two phase wires |
Inverter output voltage | AC 220V±5%,or 110V±5%,or 380V±5% |
Output frequency | 50HZ±1%,or60HZ±1%,auto stable frequency |
Output waveform | Power frequency pure sine wave,distortion rate ≤3%(linear loads), ≤5%(unlinear loads) |
Switch type | Automatically switch,0.1s-1s(zero switch on-line type inverter) |
Efficiency of the inverter | ≥85% |
Load power factor | ≥0.8 |
Output short circuit protection | ≤0.5s |
Output over load protection | 120%≥1min,150%≥10s |
Battery voltage | 24V,48V,96V,110V,192V,220,360V,380V,480V and so on |
Input DC over voltage protection | ≥130% rated voltage value |
Input DC under voltage protection | ≤85% rated voltage value |
Battery discharge time | Discharge time T(H)=battery voltage(V)×battery capacity×0.75/ loads power(W) |
Solar panel voltage | Solar panel voltage match with battery voltage |
Solar panel charge current | Interior PWM charge controller, constant voltage and limit current charge,current is based on solar panel power |
Temperature rise/℃ | The temperature of transformer rise ≤ 75℃ |
Insulation resistance | ≥20MΩ |
Dielectric strength | 1500V,1min NO breakdown |
Using environment condition | -10℃~40℃,humidity0-93% don’t have condensation,altitude≤2000m |