• The CF800X panel is available on 1,2,4 zones.
• Each zone has a maximum capacity of 50 devices.
• It has 3 groups of sounders output circuits each capable of supplying 300mA.
• It has a 24V/300mA auxiliary supply.
• It has a set of fault relay contacts,rated at 0.5A SELV.
• It has the ability to disable any zone,any group of sounder.
• The panel will send a fault signal when there is zone short/open or sounder short/open.
• It has the ability to disconnect the zones and sounders automatically when there is zone short or sounder short.After the short is clear, the zones and sounders will recover.
• It has the sounder start/stop and delay facility (the delay time is 30-120 seconds in 30 seconds increments).
• It has the frst fre alarm and subsequent fre alarm functions.
The indicator of the frst fre zone is fashing and the subsequentfre zone is lit.
• It has the mains-lost silence function.After confgure the mains-lost silence function,the panel will not send the main power lost fault signal.