Welcome Customer !

Membership

Ningbo Sentek Electronics CO.,LTD
Free Member ·1YRS
,
Other

Main Products: 电子元器件

Xwboo>Products

SD119-G 2/4 Wire Smoke Detector Sensor for Home Security System Wide Voltage Range Smoke Alarm wi...

Model
SD-119G
Nature of the Manufacturer
Other
Product Category
Conventional devices
Place of Origin
City, Province
Overview
• 2 or 4 wire models • Wide voltage range, and stable output • Advanced detection and discrimination algorithms • Easy installation and maintenance • Sleek low-profile housing design • Durable sensor head, no need for replacement • SMD circuit board design-satisfactory quality and reliability guaranteed • Integrated heat detector for SD119-2H and SD119-4H models • N/C (normal/close)-N/O (normal/open)selectable relay output • AR (Auto Reset) function for security systems (optional for 4 wire models) Sensor base opti......
Product Details


SD119-G Series

Conventional Photoelectric Smoke and Heat Alarm

All of the Sentek’s SD119-G series detectors meet the requirements of UL 268 and EN 54-7/5 for use in fire alarm signaling systems. They are intended for use in 2-wire/4-wire Class A or B supervised zone circuits. The SD119 series detectors are subject to panel compatibility limits and compliance with corresponding NFPA 72E standards, local codes, and ordinances.

The SD119-G series include 2-wire and 4-wire detectors, which provide fast and reliable response for

photoelectric smoke and heat (135°F ) detection. While the smoke and heat detection circuits operate independently, their outputs being "OR' connected, The Sentek’s SD119-G series detectors provide the fire detection performance by acting as a smoke sensor and/or a 135°F heat detector at the same location.

Product Features

•  2 or 4 wire models 

•  Wide voltage range, and stable output

•  Advanced detection and discrimination algorithms 

•  Easy installation and maintenance 

•  Sleek low-profile housing design 

•  Durable sensor head, no need for replacement 

•  SMD circuit board design-satisfactory quality and reliability guaranteed 

•  Integrated heat detector for SD119-2H and SD119-4H models 

•  N/C (normal/close)-N/O (normal/open)selectable relay output

•  AR (Auto Reset) function for security systems (optional for 4 wire models) Sensor base option:

standard and Shottky Diode

•  Five-year limited warranty

The range includes


SD119-G-2  

2 wire photoelectric smoke alarm

SD119-G-2-LED

2 wire photoelectric smoke alarm with remote LED output

SD119-G-2H  

2 wire photoelectric smoke and heat alarm

SD119-G-2H- LED 

2 wire photoelectric smoke and heat alarm with remote LED output

SD119-G- 4

4 wire photoelectric smoke detector

SD119-G- 4B

4 wire photoelectric smoke alarm with Buzzer

SD119-G- 4AR

4 wire photoelectric smoke alarm with auto-reset function

SD119-G- 4ARB 

4 wire photoelectric smoke alarm with auto-reset function and Buzzer 

SD119-G- 4H

4 wire photoelectric smoke and heat alarm

SD119-G- 4HB 

4 wire photoelectric smoke and heat alarm with Buzzer 
SD119-G- 4HAR 4 wire photoelectric smoke and heat alarm with auto-reset function 


Product  Specification


Model  

2/4 wire

Thermal

Voltage DC

Standby

Current

(Max.)

Alarm

Current

12/24V


Surge

Current

(Max.)

Star-Up

Time

(Max.)

Frequency  Alarm contact Base model

SD119-G-2 

2


10〜36V   65μA   30~40mA      150μA    20S 3 Seconds    — P/N852001

SD119-G-2L   

2


10〜36V  65μA   30~40mA      150μA     20S 3 Seconds   — P/N854001

SD119-G-2H 

2  

57°C  10〜36V  65μA   30~40mA      150μA      20S 3 Seconds   — P/N852001

SD119-G-2HL

2

57°C  10〜36V  65μA   30~40mA     150μA    20S 3 Seconds     —  P/N854001

SD119-G-4    

4


10~60V  65μA   25mA       150μA     20S 3 Seconds   Form A   P/N854001

SD119-G-4H     

4

57°C  10~60V 65μA   25mA      150μA    20S 3 Seconds   Form A   P/N854001

     SD119-G -4AR    

4


10~60V 65μA   25mA     150μA    20S 3 Seconds   Form A /Auto Reset    P/N854001

  SD119-G -4HAR      

4

57°C 10~60V  65μA   25mA      150μA    20S  3 Seconds  Form A /Auto Reset   P/N854001

  SD119-G -4B    

4


10~60V 65μA   30mA     150μA   20S  3 Seconds   Form A  P/N854001

  SD119-G -4BAR  

4


10~60V  65μA   30mA     150μA 20S 3 Seconds  Form A /Auto Reset  P/N854001

    SD119-G -4HB  

4

57°C 10~60V  65μA   30mA       150μA   20S  3 Seconds   Form A   P/N854001

    SD119-G -4HARB   

4

57°C 10~60V  65μA    30mA       150μA   20S 3 Seconds  Form A /Auto Reset  P/N854001

Remark: L- remote indicator output; H-Heat sensor; AR-Auto Reset; B-Sound

M-magnet test switch function available on special request.


Product Character


Smoke Sensitivity

0.08~0.2db/m(EN standard) or 0.98~4.0%/FT Obscuration (UL standard)

Ceiling Spacing

50 foot rating for heat sensor

Reset Voltage

less than 5 volt

Reset Time

less than 1 second

Alarm Indicator

LED continuously emitting red light

Remote Output

3.0~3.7VDC when in series a LED & 100 Ω resistor

Operating Temperature

-20°C to 80°C

Storage Temperature

-30°C to 80°C

Humidity

0 to 95% RH, no condensation or icing

Alarm Contact

(for 4-wire) NO or NC Operation, Form A: 1.0A@30VDC/0.5A@125VAC

Dimensions

100mm (dia) x 46mm (ht) with base

Weight

130g/set with base



Certificate