BV-D RESIDUAL CURRENT DEVICE
| |
| ELECTRICAL | Design according to | IEC 1008 (EN61008) | Tripping time | undelayed min.10ms delay min.40ms delay with selective disconnecting function | Rated voltage | 230/400V;50Hz | Rated tripping current | 10,30,100,300,500mA | Sensitivity | AC and pulsating DC | Rated short | 10KA with 63a gl back-up fuse | Circuit strenth | 10KA with 80A gL (F7-80 and -863) 6KA (rated current 63A) with 63A gL | Maximum back-up fuse for | 63gL | short circuit protection | 80A gL(F7-80 and -863) | maximum back-up fuse for | 45A gL(F7-25 and -40A) | Overload protection | 40A gL(F7-80A) | Resistance to climatic conditions | according to IEC 1008 | Degree of protection | built-in switch IP 40 | Endurance electrical comp. mech comp | ≤4.000 operating cycles ≥20.000 operating cycles |
| | MECHANICAL | Frame size | 45mm | Socket size | 80mm | Device width | 35mm(2mod.), 70mm(4mod.) | Mounting | quick fastening with 2 lock-in positions on DIN rail En50022 | Upper and lower terminals | Open mouthed/lift terminals | Terminal protection | Finger and hand touch sage, VBG5, OVE-EN 6 | Terminal capacity | 1--25mm2 | Busbar thickness | 0.8-2mm |
|
|
| |
 |