The controller adopts a high-power independent power supply and a reliable integrated control board, which can realize various control methods such as differential pressure, timing, manual, etc., It can realize the signal collection of the equipment, automatic operation of backwashing and protection detection. It can be used for the automatic operation control of lamination filters, shallow media filters, hydraulic drive filters, brush filters and other equipment.
Power supply of control system :AC220V,1A
Control output voltage: DC24V, switch contact 2A
Optional AC24V, switch contact 2A
Optional AC220V, switch contact 2A
Control output quantity: 2-15 filter units
Collected signal: differential pressure, maximum differential pressure value <500Kpa
Standard control methods: differential pressure, time, manual
Operating environment requirements
Indoor installation, outdoor installation needs to increase protection (please specify)
No flammable, explosive dust and gas around
Operating environment temperature: -5 ~ 40℃
Type

Integrated PLC control 2-7 Multi-channel control Save data after power off Nixie tube display Key operation setting Can add a remote communication port Can add differential pressure output signal | Integrated PLC control 2-15 Multi-channel control Save data after power off Monitor display Key operation setting Status display Can add a remote communication port Can add differential pressure output signal | Integrated PLC control 2-15 Multi-channel control Save data after power off Touch screen display Touch operation settings Status display Can add a remote communication port Can add differential pressure output signal |
Display information
0. Cleaning type; pressure difference, time, etc.
1.Regular cleaning Countdown time
2.Number of differential pressure cleanings;
3.Regular cleaning times;
4. Manual cleaning times
parameter setting
Select differential pressure cleaning, select regular cleaning, and simultaneous cleaning;
Set the cleaning pressure difference, the setting range is 10-350Kpa, and the default is 70Kpa after exceeding the range;
Set the time cleaning interval; unit minutes range 4 ~ 30000 minutes, about 20.8 days;
Set the cleaning time of each group in the range of 4-600 seconds per unit, and the default is 20 seconds after exceeding;
Proofreading of pressure sensor;
Set the number of cleaning units, 2-15 groups;
Set the interval between groups, the default is 30 seconds
Other displays and operation
Start manual cleaning.
Continuous cleaning and alarm
Sensor alarm display
After the fault is eliminated, the fault is removed.
After continuous cleaning alarm, the system will automatically switch to regular cleaning.