SF6 Switch

Model
Nature of the Manufacturer
Manufacturer
Product Category
SF6 Load Break Switch
Place of Origin
City, Province
Overview
SF6 Load switches and combiners (hereinafter referred to as "load switches" and "combiners") are suitable for three-phase ac power systems of 10kV and 50HzThis product as industrial and mining enterprises, high-rise buildings, residential quarters, pre-installed type substation, for the breaking, closing load current, the fault current, control and protection circuit and the power distribution transformer
Product Details

1

1

5


General Characteristics

Rated Voltage (kV)

7.2

12

17.5

24

36

Insulation level*

50Hz-1min (kV rms)

Insulation

20

28

38

50

70


Isolation

23

32

45

60

80

1.2/50μs (kV peak)

Insulation

60

75

95

125

170


Isolation

70

85

110

145

195

Short-time withstand current

Switch(kA/1s)

25

630A



20

630A


16

630A


12.5

630A

Disconnector(kA/1s)

25

630-1250A

1250A


20

630-1250A


16

630-1250A


12.5

630-1250A

Maximum breaking capacity

Transformer off load (A)

16

Cables off load (A)

31.5

50

Switch (A)

630

Fuse-switch** (kA)

25

20

The making capacity is equal to 2.5 times the short-time withstand current.

(*) Equipped referring to installation guide, and setting up at an altitude below 1000m.

(**) Depending on fuse characteristics

Endurance

units

Mechanical endurance

Electrical endurance

Switch

Fuse-switch

IEC62271-103

1000 operations

Class M1

IEC62271-103

100 breaks at In, p.f.=0.7

Class E3

Disconnector

IEC62271-102

1000 operations

Temperatures

The products must be stored in a dry area free from dust and with limited temperature variations

For stocking: from -40℃ to +70℃

For working: from -5 ℃ to +40℃

Other temperatures, consult us

Standards

FLN36 units meet all the following recommendations:

Switch:

IEC62271-103: High voltage switches - Part 1: switches for rated voltages above 1 kV and less or equal to 52 kV.

Disconnector:

IEC 62271-102: High-voltage alternating current disconnectors and earthing switches.

Switch /disconnector:

IEC 62271-200: A.C. metal-enclosed switchgear and controlgear for rated voltage above 1 kV and up to including 52 kV.

VPIS:

IEC 62271-206: High-voltage prefabricated switchgear and controlgear assemblies-Voltage presence indicating systems


Switch or disconnector and earthing switch

Gas tightness

The three rotating contacts are placed in an enclosure filled with gas to a relative pressure of 0.4 bar (400 hPa) for FLN36 12-24 kV and 1 bar (1000 hPa) for FLN36 36 kV.

It satisfies “sealed pressure system" requirements and seal tightness is always factory checked.


Operating safety

the switch may be in one of three positions: “closed", “open", or “earthed", representing a natural interlocking system that prevents incorrect operation.

Moving-contact rotation is driven by a fast-acting mechanism that is independent of the action of the operator.

the device combines the breaking and disconnection functions.

the earthing switch placed in the SF6 has a short-circuit making capacity, in compliance with standards.

any accidental over-pressures are eliminated by the opening of the safety membrane, in which case the gas is directed toward the back of the unit, away from the operator.