Welcome Customer !

Membership

WENZHOU MINGZHE ELECTRIC CO LTD
Free Member ·1YRS
WenZhou,ZheJiang
Manufacturer

Main Products: Other Switches|Miniature Circuit Breaker

Xwboo>Products

SF6 Load Break Switch24kv 36KV

Model
Nature of the Manufacturer
Manufacturer
Product Category
SF6 Load Break Switch
Place of Origin
City, Province
Overview
Rated Voltage:12 KV 24kV 36KVRated Current:630A;1250A
Product Details

5

1


Main technical specificationUnitFLN ⟩ -24D/T630-20 Load break switchFLRN ⟩ -24D/T100-31.5 LBS + Fuse-combination units
Rated voltageKV2424
Rated frequencyHz5050
Rated currentA630100
Short-duration(1min)power frequency withstand voltageKV6565
Lightning impulse withstand voltageKV125125
Rated power frequency withstand voltage(5min)KV2424
Rated short-time withstand current(load break switch/3s)KA2020
Rated short-time withstand current(Earthing switch/2s)KA2020
Rated peak withstand current(load break switch)KA5050
Rated peak withstand current(Earthing switch)KA5050
Rated short circuit making current(load break switch)KA50125
Rated short circuit making current(Earthing switch)KA5050
Rated closed-loop dropout currentA630
Rated active load breaking currentA630
Rated cable-charging breaking currentA1010
Rated short-circuit breaking currentKA
31.5
Rated transfer currentA
1400
Fuse type

XRNT-12KV/100A
Fuse impact output energyJ
1±0.5
Mechanical endurance LBS/Earthing switchTime3000/20003000
Air insulation distance of charged body and groundmm≥180≥180
SF6 Gas pressure(Relative pressure at 20℃)bar0.40.4
Opening and Closing simultaneityms≤2≤2


Switch or disconnector and earthing switch

Gas tightness

The three rotating contacts are placed in an enclosure filled with gas to a relative pressure of 0.4 bar (400 hPa) for FLN36 12-24 kV and 1 bar (1000 hPa) for FLN36 36 kV.

It satisfies “sealed pressure system" requirements and seal tightness is always factory checked.


Operating safety

the switch may be in one of three positions: “closed", “open", or “earthed", representing a natural interlocking system that prevents incorrect operation.

Moving-contact rotation is driven by a fast-acting mechanism that is independent of the action of the operator.

the device combines the breaking and disconnection functions.

the earthing switch placed in the SF6 has a short-circuit making capacity, in compliance with standards.

any accidental over-pressures are eliminated by the opening of the safety membrane, in which case the gas is directed toward the back of the unit, away from the operator.