How to select inverter according to load characteristics
Date: 2022/11/3Read: 38

How to select inverter according to load characteristics

Jun 28, 2022

How to select inverter according to load characteristics

The load of the inverter seems to have many types, such as extrusion, coiling, hanging objects, blowing, etc. In fact, the load can be roughly divided into ① friction load; ② gravity load; ③ fluid load; ④Inertia load. The mechanical load is generally divided into three load characteristics: ① constant torque load, ② square torque load, ③ constant power load

The relationship between load characteristics and motor output power and speed is as follows; for constant power, constant torque, square torque, decreasing power and negative torque,

①For constant torque loads, such as extruders, mixers, conveyor belts, in-plant transport trams, hoisting mechanisms, etc., if ordinary functional inverters are used, to achieve constant torque speed, enlarged motors and inverters are often used. It is more ideal if a high-function inverter with torque control function is used to realize the speed regulation operation of constant torque load. Because this kind of inverter has large torque at low speed, high static mechanical properties and high hardness, it is not afraid of load impact, and has the characteristics of excavators.

②For production machinery that requires high precision, good dynamic performance, and fast speed response, such as paper machines, injection molding machines, rolling mills, etc., high-performance general-purpose inverters with vector control or direct torque control should be used.

③For constant power loads, such as lathes, planers, blowers, etc., since there is no inverter with constant power characteristics, the U/f control method can be used to achieve constant power.

④For fan and pump loads, since the load torque is proportional to the square of the rotational speed, the load torque is small at low speed, so you can usually choose a special-purpose or general-purpose general-purpose inverter. It must be pointed out that some general-purpose inverters are suitable for all three loads, so although the general-purpose inverter is a bit more expensive, it is worth the money.

Motor power is proportional to the product of rotational speed and torque. Even for motors of the same power, the required inverter capacity is different due to different load properties. Among them, the inverter capacity required by the square torque load is lower than that of the constant torque load, so it is concluded that the inverter and the motor are combined into a variable frequency speed regulation system, and the technical parameters between the two can meet the requirements. Load torque requirements at low and high speeds. For example; the type of inverter should be selected according to the load requirements.

(1) For constant torque loads, such as extruders, mixers, conveyor belts, in-plant transport trams, hoisting mechanisms, etc., if ordinary functional inverters are used, to achieve constant torque speed regulation, an enlarged motor is often used. And the method of inverter capacity to improve low-speed torque; such as using a high-function inverter with torque control function to realize the speed regulation operation of constant torque load. is more ideal. Because this kind of inverter has large torque at low speed, high static mechanical properties and high hardness, it is not afraid of load impact, and has the characteristics of excavators. (2) For production machinery that requires high precision, good dynamic performance, and fast speed response, such as paper machines, injection molding machines, rolling mills, etc., high-performance general-purpose inverters with vector control or direct torque control should be used.

(3) For constant power loads, such as lathes, planers, blowers, etc., since there is no inverter with constant power characteristics, the U/F control method can be used to achieve constant power.

(4) For fan and pump loads, since the load torque is proportional to the square of the rotational speed, the load torque is small at low speed, so you can usually choose a special-purpose or general-purpose general-purpose inverter. Friendly reminder: some general-purpose inverters have three loads are applicable. The following points must also be paid attention to, in order to realize the reasonable matching of the inverter and the motor, to achieve the ideal speed regulation and energy-saving operation, the following issues should be paid attention to in the configuration of the two.

① Since the power output of the inverter often has high-order harmonics, it will increase the total loss of the motor. Even if it runs at the rated frequency, the output torque of the motor will be reduced, such as when the speed is adjusted above or below the rated frequency. , the rated output torque of the motor cannot be used enough. If the rated torque output is always required regardless of the speed, a motor with a larger capacity should be used with reduced capacity.

②From the perspective of efficiency (ie energy saving), the following points should be noted.

a. It is most suitable when the power value of the inverter is equivalent to the power value of the motor, so that the inverter can run at a higher efficiency.

b. When the power classification of the frequency converter is different from that of the motor, the power of the frequency converter should be as close as possible to the power of the motor, but it should be slightly larger than the power of the motor.

c. When the motor frequently starts, brakes or starts with heavy load and works frequently, a larger inverter can be selected to facilitate the long-term and safe operation of the inverter.

d. When the actual power of the motor has surplus, it can be considered to select a frequency converter with a power smaller than that of the motor, but pay attention to whether the instantaneous peak current will cause an overcurrent protection action.

e. When the power of the inverter and the motor are not the same, the settings of the energy-saving program must be adjusted accordingly to achieve a higher energy-saving effect. In the working mode of the inverter with constant U/F, the starting torque of the motor is proportional to the frequency, so when starting at low frequency, the starting torque is extremely small. For example, the output torque of a Y series motor at 10Hz is about 50% of the rated torque, so when selecting the motor type, special attention should be paid to the change of low-frequency starting torque. When starting with a load, the problem of static friction torque should be considered, and the motor must have a large enough starting torque to ensure starting with a load.