What is the appropriate starting frequency for the inverter
When the output frequency of the VFD (also called a frequency converter, VFD (Variable-frequency Drive)) is 0, the motor cannot start because the motor does not have enough starting torque. Only when the output frequency of the VFD reaches a certain value, the motor starts to accelerate, and the output frequency of the VFD is the starting frequency fs. At this time, the starting current is larger and the starting torque is larger. The setting of the starting frequency is to ensure that the motor has enough starting torque when starting, and prevent the motor from failing to start or causing overcurrent tripping during the starting process. In general, the starting frequency should be set according to the characteristics of the load driven by the VFD. On the one hand, it is necessary to avoid the low-frequency under-excitation area to ensure that the motor has sufficient starting torque; on the other hand, the starting frequency cannot be set too high, otherwise it may cause a large current impact when the motor starts, or even an overcurrent trip. The starting frequency depends on the specific load situation.
How to determine the startup frequency?
Generally, most motors start to accelerate from 0Hz, but in some special cases, it is necessary to directly accelerate from a certain frequency. At this time, the frequency output by the VFD at the moment of starting is the starting frequency. Typically, you need to set the startup frequency in the following situations.
1. A system in which multiple pumps supply water at the same time
For a system that uses multiple pumps to supply water at the same time, since there is usually a certain water pressure in the water supply pipeline, it is difficult for the pump to start if it is started at 0Hz. In this case, it is necessary to start directly from a certain frequency in order to start the rotation smoothly.
2. Load
If the VFD is driven by a load, the friction force is large when static, and it is difficult to start from 0Hz. When this happens, it is necessary to set the starting frequency to ensure that a certain starting impact force is generated at the moment of starting, so that the system can start smoothly.
3. Cone motor
In the process of starting, friction will be generated between the stator and the rotor, so it is necessary to set the starting frequency to ensure that enough magnetic flux is quickly established at the moment of starting, so that a certain air gap is maintained between the stator and the rotor, so that the motor can start smoothly.
VFD starting frequency setting method
(1) Constant torque load. Generally, the synchronous speed of the motor should not exceed the rated slip when starting. which is:
Among them, P is the number of poles of the motor; Δn——rated slip, Δn = n1-ne; N1-synchronous speed; ne-rated speed; (1) square torque load. Since the resistance torque of the square wave torque load is small at low speed, the starting frequency can be appropriately increased.
In practical applications, the starting frequency should be set reasonably to solve the problems of difficulty in starting the motor and overcurrent tripping. For motors with large starting torque, first consider setting the appropriate starting frequency parameters, and then set a reasonable torque boost curve according to the actual load. If the VFD current is too high when starting, or even an overcurrent trip occurs, it can be solved by extending the acceleration time. But generally speaking, as long as there is no excessive flow, the speed-up time should be as short as possible to improve efficiency.