How to deal with the heating problem of the inverter in the application process?
In modern industrial control, the electric drive system that uses the frequency converter to control the motor has the advantages of remarkable energy saving effect, convenient adjustment and control, simple maintenance, centralized remote control of the network, and PLC control system. These advantages of frequency converter make it widely used in the field of industrial automatic control. This paper analyzes the fault problems that occur in the application of the frequency converter, and introduces the treatment methods.
1 Some problems in inverter application
1.1 Harmonic problem
The switching devices in the main circuit of the inverter will generate harmonics during the process of turning on and off the circuit. Low-order harmonics usually have a greater impact on the motor load, causing torque ripple; but higher-order harmonics increase the leakage current of the inverter output cable, making the motor output insufficient. Harmonic interference will also cause malfunction of the relay protection device, making the measurement of electrical instruments inaccurate or even unable to work normally.
1.2 Noise and Vibration Problems
Using the frequency converter to regulate speed will produce noise and vibration, because the output waveform of the frequency converter contains high-order harmonic components. With the change of the working frequency, the fundamental wave component and the higher harmonic component change in a wide range, which may resonate with the mechanical natural vibration frequency of the motor, and this resonance is the source of noise and vibration.
1.3 Heat problems
When the inverter is running, heat is generated due to internal losses, accounting for 98% of the main circuit and about 2% of the control circuit. Meanwhile, in summer, when the ambient temperature is too high, the temperature of the inverter rises to 80~90℃. Because the inverter is an electronic device, including electronic devices and electrolytic capacitors. , the temperature is too high, it is easy to cause the failure of the components, so that the LCD screen data cannot be displayed, and the inverter protection action often occurs.
Therefore, it is necessary to suppress the harmonics output by the inverter within the allowable range, at the same time eliminate or reduce noise and vibration, and dissipate heat from the inverter to prolong the service life of the inverter.
2 Analysis and handling of some problems in the application of frequency converters
2.1 Handling of harmonic problems
To deal with the harmonic problem is to cut off the propagation path of the interference and suppress the higher harmonics on the interference source.
The cut-off interference propagation paths are:
1) Cut off the way of common ground wire to propagate interference. The grounding of the power line should be separated from the grounding of the control line, that is, connect the grounding terminal of the power supply equipment to the grounding line, and connect the grounding terminal of the control equipment to the metal casing of the equipment panel.
2) It is an effective method to eliminate the interference of the signal line and the interference source current, that is, the high-voltage cables, power cables, control cables, instrument cables and computer cables are routed separately.
There are several ways to suppress higher harmonics on interference sources:
1) Increase the internal impedance of the inverter power supply. Usually the internal impedance of the power supply can buffer the reactive power of the inverter DC filter capacitors. The higher the internal impedance, the lower the harmonic content. This internal impedance is the short-circuit impedance of the transformer. Therefore, when selecting the inverter power supply, it is best to choose a transformer with a large short-circuit impedance.
2) Install the filter. Install an LC passive filter in front of the inverter to filter out higher harmonics, usually the 5th and 7th harmonics.
3) Install the reactor. Install a line reactor on the front side of the inverter to suppress overvoltage on the power supply side.
4) Setting an active filter for active filtering automatically generates a current with the same amplitude and opposite phase as the harmonic current, so that the harmonic current can be effectively absorbed.
2.2 Dealing with noise and vibration problems
1) When the low-order harmonic component in the output of the inverter resonates with the natural mechanical frequency of the rotor, the noise increases; when the high-order harmonic component in the output of the inverter resonates with the iron core, bushing, bearing frame, etc. . Near their natural frequencies, the noise increases.
The noise generated by the inverter-driven motor, especially the harsh noise, is related to the switching frequency of the PWM control, especially in the low frequency region. In order to solve this problem, an AC reactor is usually connected to the output end of the inverter. If there is a margin in the electromagnetic torque, u/f can be set smaller to stabilize and reduce noise.
2) During the operation of the inverter, the magnetic field generated by the high-order harmonics in the output waveform will generate electromagnetic driving force for many mechanical parts, and the frequency of the driving force will resonate when it is close to or coincides with the natural frequency of these mechanical parts. . Low-order harmonic components are the main factors that have a greater impact on vibration, and have a greater impact in PAM mode and square wave PWM mode. When using SPWM, the low-order harmonic components are small, and the impact is also small.
Or the way to eliminate vibration is to connect an AC reactor on the output side of the inverter to absorb the high-order harmonic current component in the output current of the inverter. When using the PAM mode or square wave PWM mode inverter, you can use the SPWM mode inverter to reduce the pulsating torque, which can weaken or eliminate vibration and prevent mechanical parts from being damaged due to vibration.
2.3 Treatment of fever
General frequency converters are generally required to work at -10°C~+50°C. In order to ensure the reliable operation of the inverter and prolong the service life of the inverter, the inverter must be cooled. In winter, the built-in fan of the inverter can take away the heat inside the inverter box; in summer, the temperature itself is 40°C, and the internal heat taken away by the built-in fan of the inverter can only increase the indoor temperature and the temperature of the inverter box. At this time, the best way is to make several φ500mm holes evenly and appropriately on the wall next to the inverter box in the power distribution room, and at the same time ensure that there is a certain space around the inverter in the control cabinet and keep it intact. If this does not work, turn on the fan, or install an exhaust fan and air duct in the hole to force the heat generated by the inverter out of the room. Finally, consider using air conditioners to force the cooling of the space where the frequency converter is installed.
Conclusion 3
It is very necessary to strengthen the research on faults in the application of frequency converters, which is of great significance to the normal use of frequency converters, tapping potentials and increasing efficiency.