In the bearing holding mode, the inverter has a protection failure problem, how to rectify it?
Date: 2022/11/3Read: 34

In the bearing holding mode, the inverter has a protection failure problem, how to rectify it?

Mar 29, 2022

In the bearing holding mode, the inverter has a protection failure problem, how to rectify it?

A company's EVA plant designed 13 silos, installed 14 degassing fans, one degassing fan corresponds to one silo, and the other degassing fan is a backup fan. When a silo degassing fan fails and stops, the standby degassing fan is automatically started, and the short-term shutdown of the fan has no effect on production.

The equipment adopts German Aizhen GM801 fan; the motor adopts Siemens 1LE0002-3AA2 3-3AB4-Z 315M, rated power 132kW, rated current 235A, rated speed 2980r/min; fan and motor use belt to transmit power; control mode adopts frequency conversion The motor starts; the motor is installed on the cantilever elastic foundation.

At present, a number of motor shaft bearing accidents have occurred during the operation of the equipment. The on-site inspection of the motor cannot be turned, the bearing temperature is high, and the rotor shaft of the motor is ground and needs to be repaired by an external contractor.

1 Fault phenomenon

1.1 Damage to the motor bearing

Since the operation of the equipment in 2013, many motors of the EVA air supply system have shown the phenomenon that the drive end bearing holds the shaft, and the motor bearing is faulty. The bearing temperature is measured at about 200°C on site.

The dismantling and inspection found that the inner ring of the motor drive end bearing has a running sleeve phenomenon, the motor rotor shaft is ground fine, and the inner and outer oil caps are worn to varying degrees. Need to be outsourced to repair the shaft size, resulting in increased maintenance costs.

1.2 Protection action situation

SIS displays "low flow" or "low pressure" process interlock trip; the inverter has no fault trip record, and it is displayed as a normal stop.

2 Reason analysis

2.1 Analysis of the reasons for the motor bearing holding the shaft

According to ISO 10816 "International Standard for Vibration Judgment of Rotating Machines", the vibration of 132kW motor should not be greater than 4.5mm/s, the vibration alarm value of Aizhen fan is 11mm/s, and the vibration jump value is 18mm/s. In actual operation, the motor often exceeds the allowable vibration standard value, resulting in accelerated motor bearing damage.


The motor has a refueling hole, but no oil drain hole, so the waste oil cannot be discharged online. After refueling for a certain period, there is too much waste grease in the bearing chamber, and the space of the bearing chamber is limited. In addition, the motor rotates at a speed of 2985r/min, which causes the motor bearing to run. temperature rises.


The Roots blower is noisy, and the abnormal running sound of the bearing is covered by the noise of the Roots blower. Sometimes the inspection personnel cannot find the abnormal running state of the motor bearing in time. Combining the above three factors is the main reason for the bearing holding the shaft of the motor.


2.2 Analysis of the reasons why the inverter has no fault tripping


There is a process from the normal operation of the motor bearing to the locking of the bearing, which takes several minutes or ten minutes. If the inverter can protect and trip in time according to the increase of operating current caused by the fault of the motor bearing, it will not extend the fault of the motor bearing to the phenomenon of the motor bearing holding the shaft, or to the accident of serious wear of the motor rotor shaft. Check the inverter thermal protection and stall protection parameter settings.

By checking the protection parameters of the inverter, it is found that the thermal overload protection of the motor does not work. Therefore, after the motor bearing is damaged, although the running current increases to reach the thermal overload action value, the inverter does not put into thermal overload protection, so the inverter will not act due to thermal overload protection. And tripped.


The inverter stall protection time is 20s, and the stall protection setting stall frequency is 20Hz. After the equipment stalls, the inverter output frequency drops to 20Hz, and the inverter will trip when the stall time reaches 20s. The "low flow" and "low pressure" process interlocks reach the protection action value, and the car trips in 0.5s. Because the motor bearing failure causes the fan speed to decrease and the air volume to decrease, the process interlock trip takes priority over the inverter stall protection trip, and the inverter stall protection does not work.


3 Corrective measures


3.1 Corrective measures to prevent the motor bearing from sticking to the shaft


Strengthen the maintenance of the Roots blower, correct the vibration of the motor in a timely manner, control the vibration value of the motor within the normal range, and strictly prohibit the operation of the motor exceeding the standard value of vibration. Check "Electrical Manufacturing Technology". The depth tolerance code of the bearing chamber of the domestic motor is h11, which is the same as the depth tolerance code of the bearing chamber of the Siemens motor. The fixed size of the 315M outer bearing cover is the same, and the domestic motor Y2-315-4 outer bearing cover has an oil drain hole, which can realize the online oil drain function of the motor.

The outer bearing cover of the domestic motor is replaced by the outer bearing cover of the Siemens motor to realize the online oil draining and oil changing function of the motor, and avoid excessive waste grease in the bearing chamber of the motor, excessive temperature of the motor bearing, and occurrence of the bearing shaft accident.


3.2 Rectification measures for inverter protection parameter setting


After many on-site observations, when the inverter of the EVA silo degassing fan starts, the inverter current does not exceed 120A; the maximum normal operating current is in the range of 120-140A, the maximum operating current does not exceed 150A, the rated current of the motor is 235A, and the actual operating current of the motor It is 85A smaller than the rated current of the motor, which is called half-load load. If the thermal overload protection of the inverter is set according to the rated current of the motor, even if the thermal overload protection of the inverter is activated, when the motor bearing fails, the thermal overload trip protection of the inverter cannot occur.


Considering the actual operation of the motor, a certain safety factor is reserved for the thermal overload protection of the inverter. 30.04MOTOR THERM PROT motor temperature protection selects FAULT fault tripping; 30.05MOT THERM P MODE motor thermal protection mode selects USER MOODE user mode; 30.06MOTOR THERM TIME thermal time constant is set to 256s; 30.07MOTOR LOAD CURVE allows motor overload continuous current at 170A Consider, set to 72.3%; 30.08ZERO SPEED LOAD allowable motor continuous current at zero speed is set to 51%; 30.09BREAK POINT 99% load The drive output frequency is set to 50Hz.


Inverter stall protection, 30.11STALL FREQ HI is changed from the original stall frequency 20Hz to 47Hz; 30.12STALL TIME stall time is modified from the original 20s to 10s.


Consult the inverter manual, 32 SUPERVISION is the monitoring limit value, and has the function of motor current monitoring and alarm output.


Set 32.05CURRENT FUNCTION motor current monitoring function and select the type of limit value monitoring to HIGH LIMIT upper limit; 32.06CURRENT LIMIT motor current monitoring limit value is set to 170A; 14.01 RELAY RO1 OUTPUT selects the transmission status displayed by relay output RO1 to be set to The motor current monitoring limit value is reached; 14.04 RO1 TON DELAY delay pick-up time is set to 3s; 14.05 RO1 TOFF DELAY delay release time is set to 1s.

The normally open contact of the limit current monitoring relay RO1 controls the intermediate relays KA6 and KA6 normally closed contacts in series with the inverter starting circuit. When the motor running current reaches 170A, the relay RO1 delays 3s to start the intermediate relays KA6 and KA6 normally closed contacts Disconnect the inverter starting circuit, the inverter stops output, and the motor stops. At the same time, the KA6 normally open contact is self-retaining, and the KA6 intermediate relay has its own power-on indicator, which is convenient for electrical operators to find out the reason for the inverter to trip.


4 Conclusion


1) Larger power motors are designed with online oil discharge function


Domestic Wolong Electric Nanyang Explosion-proof Group Co., Ltd., HE Group Jiamusi Electric Motor Co., Ltd. and foreign ABB companies, 11kW and above power motors can be designed and installed online oil injection and oil discharge holes.


It is suggested that when Party A purchases a motor with a power of 11kW and above, it is required that the motor has the functions of online oil injection and oil discharge hole. Replacing the grease online by the motor can prolong the service life of the motor bearing, reduce the labor intensity of electrical maintenance personnel, prolong the motor maintenance cycle, reduce equipment maintenance costs, and reduce enterprise operating costs.


2) Set the thermal protection current according to the actual maximum operating current


There are a few motors in the production site that have half-load loads. The normal running current of the half-loaded motor is much lower than the rated current of the motor. When the motor bearing or the bearing of the dragging equipment fails, the running current of the motor increases. If the thermal overload protection of the inverter is set according to the rated current of the motor, the thermal overload protection of the inverter generally does not trip, and the motor continues to run for a long time in the case of bearing failure, resulting in further expansion of the mechanical failure of the equipment.

In order to realize the reliable protection of the half-loaded motor inverter to the equipment bearing fault, it is recommended to set the inverter thermal overload protection according to the reliability factor of multiplying the maximum current of the motor in normal operation by 1.05 to 1.2 times, so as to improve the thermal overload protection of the inverter. reliability.


3) Inverter adds definite time overcurrent protection function


If the motor-driven equipment trips, the impact on production is small, in order to enable the inverter to reliably protect the bearing failure of the motor or the motor-driven equipment, according to the actual situation on the spot, the inverter passes 32 sets of limit monitoring values. Current protection function. For the definite time overcurrent protection of the inverter with half-load load, it is recommended to set the overcurrent protection value according to the maximum current value of the motor in daily operation times the reliability factor of 1.1 to 1.3 times. fault protection range.


In actual operation, the bearing fault of the motor leads to the bending of the motor shaft, the scavenging of the rotor or the shaft breaking accident. Most of them are the thermal overload protection and timing overcurrent protection of the motor with half-load load. The starting threshold value is set according to the rated current of the motor, ignoring the half-load load. The fact that the maximum current of the motor in daily operation is smaller than the rated current of the motor.


When the bearing of the half-loaded motor is faulty, although the motor running current is higher than the maximum current of the motor in normal operation, it does not reach or does not reach the starting threshold value of the thermal overload protection and timing overcurrent protection of the protection device in time, and the motor protection device fails to protect the trip in time. , The motor runs for a long time in the case of bearing failure, which is further expanded to the bending of the motor shaft and the sweeping of the motor rotor. The modified equipment works well.