Analyze how to choose the inverter model for high-power motors
In order to allow the motor to achieve higher efficiency and controllable working conditions, and to avoid wasting the power of the motor drive system, frequency converters came into being. However, due to the various types of motor loads, the functional requirements of the equipped inverters are also different, so how to choose a suitable inverter for the motor? These are all questions facing engineers.
The principle of the frequency converter is applied to the principle of frequency conversion and electronic information technology, and the output power transmission component of the AC motor is manipulated according to the frequency and amplitude value of the alternating current.
The inverter should be selected according to the control target type, static speed accuracy, speed adjustment range, starting torque and other factors, to consider the corresponding model of the inverter. It is easy to use and economical while meeting the process and production requirements. And choosing the right frequency converter for the entire motor system is even more a headache.
Strictly speaking, the size of the rated power of the motor is not directly related to the selection of the inverter. The selection of the inverter model is generally based on the load type of the motor drive, such as cranes, cranes, metal wire drawing equipment, mining crushing and other high-load equipment must be two specifications larger than the motor.
Second, it depends on the rated current of the motor. The rated output current of the inverter is greater than the rated current of the motor. Ordinary fans and water pumps can be matched 1:1 with light-load F-type inverters; general machinery can be matched 1:1 with heavy-duty G-type inverters; Roots blowers and submersible pumps should use inverters of the same power and heavy load. .. There is also the influence of altitude and temperature.
When the high-power motor is started, the frequency converter can achieve the advantages of smooth motor starting current and no impact. The inverter is also an intelligent device in the speed control circuit. Stable speed regulation. The distance of the force is equal. The common AC contactor in the electromagnetic starter will generate a large inrush current when it is started directly. For motors with large equipment losses. Both 400 volts and 18.5 kilowatts can be used, but the price of the frequency converter is higher.
When selecting the inverter, the actual current value of the motor should be used as the basis for selecting the inverter, and the rated power of the motor can only be used as a reference. In addition, the fact that the inverter output contains a large number of high-order harmonics should be fully considered, which will reduce the power factor and efficiency of the motor.
Therefore, compared with supplying power to the commercial power grid using a frequency converter, the motor current increases by 10%, and the temperature rise increases by about 20%. Therefore, when selecting motors and inverters, considering this situation, in order to prevent excessive temperature rise and affect the life of the motor, it is necessary to leave a margin.
The overload torque of most series motors is generally 212 ~ 218 times. In order to give full play to the load capacity of the motor and improve the safety performance of potential energy load equipment, after the inverter is used for control, it is necessary to ensure that the overload capacity of the inverter-motor system is 212 to 218 times.
Since the normal inverter has an overload capacity of 150% rated load for 1 minute, the instantaneous overload torque can only reach 180% ~ 200%, so it is necessary to increase the capacity of the inverter to improve the instantaneous overload of the inverter-motor system ability.
Only by increasing the capacity of the inverter by about 20%, the instantaneous overload capacity of the inverter motor system can be increased by 210 to 214 times, which is basically sufficient. Therefore, please select an inverter with a rated capacity of 120% or more of the rated capacity of the motor, that is, increase the capacity of the inverter by one level.