How to judge the quality of the soft starter and the failure phenomenon and the cause?
How to use a scientific method to judge the fault location from the fault indication of the high-voltage soft start cabinet
In the application process of the soft start cabinet, as long as we adopt scientific methods, start with the fault indication of the high-voltage liquid soft start cabinet, and consider the possible causes from the aspects of mechanical transmission, electrical control, environmental conditions, operation, control methods, and control principles. , You can smoothly solve various problems and ensure the healthy and stable operation of the equipment. Next, the editor will take you to understand the reasons for the common faults of the soft start cabinet. How to use a scientific method to judge the fault from the fault indication of the high-voltage soft-start cabinet!
1. During the commissioning process of the soft starter cabinet, there is a phase loss fault in the start report, the soft starter fault light is on, and the motor does not respond. The reasons for the failure may be:
(1) When the starting mode is electrified, the operation sequence is wrong (the correct operation sequence is to send the main power supply first, then the control power supply).
(2) Power supply lacks phase, soft starter protection action (check power supply)
(3) The output terminal of the soft starter is not connected to a load (the soft starter can only work normally after the output terminal is connected to a load)
2. When the user finishes starting the soft start cabinet, the bypass contactor does not close. The cause of the failure may be:
(1) During the start-up process, the protection device malfunctions due to a small setting. (Just reset the protection device)
(2) During debugging, the parameter setting of the soft starter is unreasonable. (Mainly for the soft starter below 55KW, reset the parameters of the soft starter)
(3) Poor contact of the control circuit (check the control circuit)
3. The user occasionally jumps the air switch during the starting process. The reasons for the failure are:
(1) The setting value of the long delay time of the air switch is too small or the air switch selection and the motor are not matched. (The parameters of the air switch are appropriately enlarged or the air switch is re-selected)
(2) The initial voltage parameter setting of the soft starter is too high or the starting time is too long. (According to the load situation, the starting voltage should be appropriately reduced or the starting time should be appropriately shortened.)
(3) Due to the large fluctuation of the grid voltage during the starting process, it is easy to cause the soft starter to issue wrong commands. There is an early bypass phenomenon. (It is recommended that users do not start high-power motors at the same time,)
(4) Start at full load when starting (Try to reduce the load when starting)
4. When the user uses the soft starter, there is no display on the screen or garbled characters, and the soft starter does not work. The cause of the failure may be:
(1) The internal wiring of the soft starter is loosened due to the vibration generated by the external components during the use of the soft starter (open the cover of the soft starter and re-plug the display screen connection)
(2) The control board of the soft starter is faulty (contact the manufacturer to replace the control board)
5. The soft starter reports a fault when starting, the soft starter does not work, and the motor does not respond. The cause of the failure may be:
(1) Motor phase loss (check motor and peripheral circuit)
(2) The main component SCR in the soft starter is short-circuited (check whether the motor and grid voltage are abnormal. Contact the manufacturer to replace the SCR)
(3) Filter board breakdown and short circuit (replace the filter board)
6. When the soft starter starts the load, the start overtime occurs. The soft starter stops working and the motor stops freely. The reasons for the failure are:
(1) The parameter setting is unreasonable (re-tuning the parameters, the initial voltage is appropriately increased, and the time is appropriately lengthened)
(2) Full load start when starting, (the load should be reduced as much as possible when starting)
7. During the starting process, the current is unstable and the current is too large. The reasons may be:
(1) The ammeter indication is inaccurate or does not match the transformer (replace a new ammeter)
(2) The grid voltage is unstable and the fluctuation is relatively large, causing the soft starter to malfunction (contact the manufacturer to replace the control board)
(3) The parameter setting of the soft starter is unreasonable. (Re-tuning parameters)
8. Repeated start of the soft starter. The reasons for the failure are:
During the starting process, the peripheral protection components act, and the contactor cannot be closed, causing the soft starter to repeatedly start (check the peripheral components and wiring)
9. The overheating fault light is on when starting, and the soft starter stops working:
(1) Frequent starting, resulting in excessively high temperature, causing the soft starter to overheat protection. (The number of starts of the soft starter should be controlled to no more than 6 times per hour, especially for heavy loads.)
(2) During the starting process, the protective element acts to prevent the contactor from bypassing, and the soft starter works for a long time, causing the protective action. (Check the peripheral circuit)
(3) Overheating protection caused by overloading and starting time is too long. (When starting, reduce the load as much as possible)
(4) The parameter setting of the soft starter is unreasonable. The time is too long and the starting voltage is too low. (Increase the starting voltage)
(5) The cooling fan of the soft starter is damaged and cannot work normally. (Replace the fan)
10. SCR damage:
(1) When the motor is starting, the overcurrent will break down the soft starter (check whether the power of the soft starter matches the power of the motor, and whether the motor is starting with load)
(2) The cooling fan of the soft starter is damaged (replace the fan)
(3) Frequent starting, high temperature will damage the SCR (control the number of starts)
(4) The filter board is damaged (replace damaged components)