After the motor starts, it stops automatically. What is the cause of the load short-circuit fault displayed on the soft starter?
There are several possibilities that cause the soft starter to display the load short circuit:
1. The connecting wire between the motor and the soft starter is short-circuited or the motor has been damaged (check the motor connection and whether the motor is damaged).
2. Overcurrent will break down the soft starter (check whether the power of the soft starter matches the power of the motor, and whether the motor is started with load).
3. The cooling fan of the soft starter is damaged (replace the fan).
4. Frequent starting, high temperature will damage the SCR (control the number of starts).
5. The filter board is damaged (replace damaged components).
1. Soft starter
Soft starter (soft starter) is a novel motor control device that integrates motor soft start, soft stop, light load energy saving and multiple protection functions. It is called Soft Starter abroad. The soft starter uses a three-phase parallel thyristor as a voltage regulator, which is connected between the power supply and the motor stator. Such a circuit is a three-phase fully controlled bridge rectifier circuit. When using the soft starter to start the motor, the output voltage of the thyristor gradually increases, and the motor gradually accelerates until the thyristor is fully turned on. The motor works on the mechanical characteristics of the rated voltage to achieve smooth starting, reduce the starting current, and avoid starting over-current tripping. When the motor reaches the rated number of revolutions, the start-up process ends, and the soft starter automatically replaces the thyristor that has completed the task with a bypass contactor to provide rated voltage for the normal operation of the motor to reduce the heat loss of the thyristor and extend the service life of the soft starter , Improve its work efficiency, and make the grid avoid harmonic pollution. The soft starter also provides a soft stop function. The soft stop is the opposite of the soft start process. The voltage gradually decreases and the number of revolutions gradually drops to zero to avoid the torque impact caused by the free stop.
Soft starter
2. Main functions
1. Overload protection function: The soft starter introduces a current control loop, so it can track and detect the change of the motor current at any time. By increasing the setting of overload current and inverse time control mode, the overload protection function is realized. When the motor is overloaded, the thyristor is turned off and an alarm signal is issued.
2. Phase loss protection function: When working, the soft starter detects the changes of the three-phase line current at any time, and once the current is cut off, it can make a phase loss protection response.
3. Overheating protection function: The temperature of the thyristor radiator is detected by the internal thermal relay of the soft starter. Once the radiator temperature exceeds the allowable value, the thyristor will be automatically turned off and an alarm signal will be issued.
4. The function of measuring loop parameters: When the motor is working, the detector in the soft starter always monitors the running state of the motor, and sends the monitored parameters to the CPU for processing, and the CPU analyzes, stores, and displays the monitored parameters. Therefore, the motor soft starter also has the function of measuring loop parameters.
5. Other functions: through the combination of electronic circuits, other interlocking protections can also be realized in the system.