How to maintain the inverter and which accessories are regularly replaced?
Date: 2022/11/4Read: 33

How to maintain the inverter and which accessories are regularly replaced?

Sep 29, 2021

How to maintain the inverter and which accessories are regularly replaced?

1. Before the inverter is powered on


The temperature and humidity of the surrounding environment should be checked first. Excessive temperature will cause the inverter to overheat and alarm. In severe cases, it will directly cause damage to the inverter's power devices and circuit short-circuits; too much air will cause a direct short-circuit inside the inverter. When the inverter is running, pay attention to whether the cooling system is in production, such as whether the air duct is smoothly exhausted, and whether the fan makes abnormal noises. Generally, inverters with relatively high protection levels, such as: inverters above IP20 can be installed directly, and inverters below IP20 should generally be installed in cabinets. Therefore, how the heat dissipation effect of the inverter cabinet will directly affect the normal operation of the inverter, Exhaust system, such as whether the fan rotates smoothly, whether there is dust and obstructions in the air inlet, are places that cannot be ignored in our daily inspection. Whether the motor reactors, transformers, etc. are overheated or smelly; whether the inverter and motor have abnormal noise; whether the inverter panel current display is too large or the current change range is too large, and whether the output UVW three-phase voltage and current are balanced.


2. Regular maintenance


Regularly remove dust to check whether the air inlet of the fan is blocked, and clean the air filter cooling duct and internal dust every month.


Regular inspection should be carried out once a year: check whether the screws, bolts and plug-ins are loose, whether the input and output reactors are short-circuited to the ground and the phase-to-phase resistance, which should normally be greater than tens of megohms. Whether the conductors and insulators are corroded, if any, wipe them clean with alcohol in time. Measure the stability of the output circuit voltage of the switching power supply, such as: 5V, 12V, 15V, 24V, etc. Whether the contacts of the contactor have traces of ignition, if it is serious, replace a new contactor of the same model or greater than the original capacity; confirm the correctness of the control voltage, and conduct a sequential protection action test; confirm that the protection display circuit is not abnormal; confirm that the inverter is in The balance of the output voltage when running alone.


Carefully do the daily maintenance and overhaul of the inverter, mainly including:


1. Dust the frequency converter regularly, focusing on the rectifier cabinet, inverter cabinet and control cabinet. If necessary, remove the rectifier module, inverter module and the circuit board in the control cabinet for dust removal. Whether the lower air inlet and upper air outlet of the inverter are dusty or blocked due to excessive dust. The inverter requires a large amount of ventilation due to its own heat dissipation, so after a certain period of operation, the surface dust is very serious, and it must be cleaned and dusted regularly.


2. Open the front door of the inverter, disassemble the back door, carefully check whether the AC and DC busbars are deformed, corroded, or oxidized, whether the screws at the busbar connection are loose, and whether the solid screws at each installation fixing point are loose or fixed. Whether the insulating sheet or insulating post is aging, cracked or deformed, if so, it should be replaced in time and re-tightened. The deformed busbar must be corrected and reinstalled.


3. After removing dust from circuit boards and busbars, perform the necessary anti-corrosion treatment, paint with insulating paint, and remove the burrs of the busbars that have appeared partial discharge and arcing before processing. For the insulation board that has been insulation breakdown, the damaged part must be removed, and the insulation board of the corresponding insulation level shall be used to isolate it near the damage. The insulation shall be tightened and tested and the insulation shall be deemed qualified before being put into use.


4. Whether the fan in the rectifier cabinet and inverter cabinet is running and rotating normally, turn it by hand when shutting down, observe whether the bearing is stuck or noise, replace the bearing or repair it if necessary.


5. Perform a comprehensive inspection of the input, rectifier and inverter, and DC input fast melting, and replace it if it is burned.


6. Whether the capacitor in the intermediate DC circuit is leaking, whether the shell is expanded, bubbling or deformed, whether the safety valve is broken, if possible, test the capacitance, leakage current, withstand voltage, etc., and for those that do not meet the requirements Replace the capacitor. For new capacitors or capacitors that have not been used for a long time, they must be passivated before replacement. The service life of the filter capacitor is generally 5 years. If the capacitor capacity, leakage current, withstand voltage and other indicators have significantly deviated from the test standard when the service time is more than 5 years, they should be replaced partially or completely as appropriate.


7. Conduct electrical inspections on the diodes of the rectifier and inverter parts and the GTO with a multimeter, measure the forward and reverse resistance values, and make a careful record in the pre-made form to see if the resistance between the poles is normal. Whether the components of the same model are in good consistency, replace them if necessary.


8. Check the main contactors and other auxiliary contactors in the A1 and A2 incoming cabinets, carefully observe whether the dynamic and static contacts of each contactor have arcing, burrs or surface oxidation, or unevenness. If such problems are found, they should be dealt with accordingly. The dynamic and static contacts are replaced to ensure that the contact is safe and reliable.


9. Carefully check whether the terminal block is aging, loose, whether there is a hidden fault of short circuit, whether the connection of each connection wire is firm, whether the wire skin is damaged, and whether the plug connection of each circuit board is secure. Whether the main power cord connection is reliable, whether the connection is heated or oxidized, and whether the grounding is good.


10. Whether the reactor has abnormal buzzing, vibration or stale smell.


In addition, if conditions permit, the filtered DC waveform, inverter output waveform and input power harmonic components can be measured.


3. Replacement of spare parts


The inverter is composed of many components, some of which will gradually degrade and age after long-term operation. This is also the main reason for the inverter failure. In order to ensure the long-term normal operation of the equipment, the following components should be replaced regularly:


1. Cooling fan


The power module of the frequency converter is a serious heating device, and the heat generated by its continuous operation must be discharged in time. The life of the general fan is about 10kh~40kh. According to the continuous operation of the inverter, the fan needs to be replaced every 2~3 years. Direct cooling fans are divided into two lines and three lines. One line of the second line fan is positive and the other line is negative. Do not connect wrongly when replacing; , There is a detection line outside the negative pole, please pay attention when replacing it, otherwise it will cause the inverter to overheat and alarm. The AC fan is generally divided into 220V and 380V, and the voltage level should not be mistaken when replacing it.


2. Filter capacitor


Intermediate DC loop filter capacitor: also known as electrolytic capacitor. Its main function is to smooth the DC voltage and absorb low-frequency harmonics in the DC. The heat generated by its continuous operation and the heat generated by the inverter itself will accelerate the drying of its electrolyte. Directly affect the size of its capacity. Under normal circumstances, the service life of the capacitor is about 5 years. It is recommended to check the capacity of the capacitor regularly once a year. Generally, a new filter capacitor should be replaced when the capacity is reduced by more than 20%.