What is the difference between inverter overload and overcurrent?
Date: 2022/11/4Read: 31

What is the difference between inverter overload and overcurrent?

Sep 13, 2021

What is the difference between inverter overload and overcurrent?

Overload is a time concept. It is a continuous time, which means that the load exceeds a certain multiple of the rated load in a continuous time.


Overcurrent is a quantitative concept. The time of overcurrent is very short, which refers to how many times the load suddenly exceeds the rated load.


Overcurrent and overload are the most common faults of the inverter. To distinguish whether the inverter is overcurrent trip or overload trip, we must first understand the difference between them. Generally speaking, overload must also overcurrent, but why does the inverter need Separate overcurrent and overload?


The main differences are as follows:


(1) The rate of change of current is different


Overload protection occurs during the working process of production machinery, and the current change rate di/dt is usually small;


Except for overload, other overcurrents are often sudden, and the rate of change di/dt of the current is often larger.


(2) Different protection objects


Because the capacity of the inverter sometimes needs to be increased by one or two gears than the capacity of the motor, in this case, when the motor is overloaded, the inverter may not overcurrent.


The overload protection is carried out by the electronic thermal protection function inside the inverter. When the electronic thermal protection function is preset, the "current draw ratio" should be accurately preset, that is, the percentage of the ratio of the rated current of the motor to the rated current of the inverter:


IM%=IMN*99%I/IM where:


IMN—the rated current of the motor, A;


IM%—current draw ratio;


IN—The rated current of the inverter, A.


(3) Overload protection has inverse time characteristics


Overload protection is mainly to prevent the motor from overheating, so it has an "inverse time limit" characteristic similar to that of a thermal relay. In other words, if the current is less than the rated current, the allowable operating time can be longer, but if the current is greater than the rated current, the allowable operating time will be shorter. In addition, as the frequency decreases, the heat dissipation of the motor will become worse. Therefore, in the case of 50% overload, the lower the frequency, the shorter the allowable running time.