How to control the leakage current hazards of photovoltaic inverters
Photovoltaic inverter is a very important device of photovoltaic system. Its main function is to convert the direct current from photovoltaic components into alternating current. In addition, the inverter also undertakes to detect the running status of components, power grid and cables, and communicate with the outside world. , System security butler and other important functions.
In the photovoltaic industry standard NB32004-2013, the inverter has more than 100 strict technical parameters, and each parameter is qualified to get a certificate.
The General Administration of Quality Supervision, Inspection and Quarantine of the People's Republic of China also conducts random inspections every year for the protection connection, contact current, power frequency withstand voltage of solid insulation, rated input and output, conversion efficiency, harmonics and waveform distortion, and power factor of photovoltaic grid-connected inverter products. , DC component, AC output side over/under voltage protection, etc. 9 items are tested. A brand new inverter, from development to mass production, takes more than two years to come out. In addition to over-voltage protection and other functions, the inverter also has many little-known high-tech methods, such as leakage current control, Thermal design, electromagnetic compatibility, harmonic suppression, efficiency control, etc. require a lot of manpower and material resources to develop and test.
This article mainly introduces the leakage current control technology of the inverter
1. Why does the photovoltaic system produce leakage current?
Photovoltaic system leakage current, also known as square matrix residual current, is essentially common-mode current. The reason is that there is a parasitic capacitance between the photovoltaic system and the ground. When the parasitic capacitance-photovoltaic system-grid forms a loop, the common mode The voltage will generate a common mode current on the parasitic capacitance. When a power frequency transformer is installed in the photovoltaic system, the parasitic capacitance impedance between the transformer windings in the loop is relatively large, so the common mode current generated by the common mode voltage in the loop can be suppressed to a certain extent. However, in a photovoltaic system without a transformer, the loop impedance is relatively small, and the common-mode voltage will form a large common-mode current on the parasitic capacitance between the photovoltaic system and the earth, that is, leakage current.
2. The harm of leakage current
The leakage current in the photovoltaic system, including the DC part and the AC part, if it is connected to the grid, it will cause grid-connected current distortion, electromagnetic interference and other problems, which will affect the operation of the equipment in the grid; the leakage current may also charge the inverter shell , Will pose a threat to personal safety.
3. Standards and detection methods of leakage current
According to Article 7.10.2 of the NB32004-2013 standard, when the inverter is connected to the AC grid and the AC circuit breaker is closed, the inverter shall provide leakage current detection. Leakage current detection should be able to detect the total (including DC and AC parts) effective value current, continuous residual current, if the continuous residual current exceeds the following limits, the inverter should be disconnected within 0.3s and send a fault signal:
1) For inverters whose rated output is less than or equal to 30KVA, 300mA;
2) For inverters with a rated output greater than 30KVA, 10mA/KVA.
Photovoltaic system leakage current has two characteristics. One is that the components are complex, with a DC part and an AC part. The second is that the current secondary value is very small, at the milliampere level, which requires extremely high accuracy and requires a dedicated current sensor. The photovoltaic standard stipulates that the detection of photovoltaic leakage current must use Type B, which is a current sensor that can measure both AC and DC leakage current.
The leakage current sensor is installed on the output interface of the inverter's external ground wire to detect the current of the inverter's output ground wire.
4. Leakage current control technology
At present, leakage current suppression technology has become a hot issue in the research of photovoltaic grid-connected systems. University research institutions and manufacturers are studying it. The magnitude of leakage current depends on the parasitic capacitance Cpv between the photovoltaic PV and the ground, and the change of the common mode voltage. The value of parasitic capacitance is related to factors such as external environmental conditions, photovoltaic panel size and structure, generally around 50~150nF/kW, and the common-mode voltage change rate is related to the inverter topology, modulation algorithm and other factors.
For the traditional single/three-phase transformerless photovoltaic grid-connected inverter topology, the two basic conditions for effective suppression of common mode current (leakage current) are: the inductance value of each bridge arm is selected the same; non-zero vector is used to synthesize the reference vector, so that The common mode voltage remains constant.
(1) Full H4 bridge topology
In order to solve the problem of leakage current in the full H-bridge photovoltaic inverter, bipolar PWM modulation can be used. This modulation eliminates the high frequency component of the common mode voltage to the board, so that the common mode voltage generally has only the low frequency component of the first harmonic, thereby reducing the impact of leakage current.
(2) H5 topology
This topology requires only one additional transistor compared to the full bridge, which is why it is named H5. During the current freewheeling period, the photovoltaic cell is disconnected from the grid to prevent the voltage between the two poles of the panel from fluctuating with the switching frequency, thereby keeping the common mode voltage almost unchanged.
(3) HERIC topology
The HERIC AC bypass topology works as follows: During the positive half cycle, switch S5 is always off and S6 is always on, and S1 and S4 are modulated at the switching frequency. When S1 and S4 are turned on, the sum voltage is Udc and 0 respectively, and the common mode voltage = Udc/2; when S1 and S4 are turned off, the current flows through the anti-parallel diodes of S6 and S5, and the voltage is Udc/ 2. At this time, the common mode voltage = Udc/2.
(4) H6 topology
The H6 DC bypass topology works as follows: During the positive half cycle, switches S1 and S4 are always on, and S5, S6, S2, and S3 are turned on alternately. When S5 and S6 are on and S2 and S3 are off, the common mode voltage = Udc/2 at this time; when S2 and S3 are on and S5 and S6 are off, there are two current freewheeling paths: (1) S1 , S3 anti-parallel diode, (2) S4, S2 anti-parallel diode. Diodes D7 and D8 clamp the voltage to Udc/2, and the common mode voltage = Udc/2 at this time.
The common mode voltage in the negative half cycle is also Udc/2, so the leakage current can be effectively suppressed.
(5) H6.5 topology
The H6.5 topology is improved on the basis of HERIC. Compared with the traditional HERIC, there is one diode less, so the efficiency will be relatively higher than that of HERIC. When reactive power exchange does not pass through the bus capacitor, the working mode voltage is one-half of the bus voltage in the switching state, so the working mode current will be very small; at the same time the output is three-level, the volume of the filter core can be further reduced and further improved Efficiency: At the same time, the middle horizontal tube is a boost chip, which is further optimized in terms of switching loss, which further improves the efficiency of the whole machine. On the other hand, there are module packages now, so that the junction temperature of the chip can be compared with the traditional single tube will be improved, which can significantly improve product reliability.
In addition to the above several topological structures, the use of multi-level technologies such as 3-level or 5-level can reduce the voltage between the positive and negative poles of the component to the ground and also reduce the leakage current.
5. Things to pay attention to when installing the system
Leakage current is detected by the current of the inverter ground wire. Therefore, during installation, the inverter ground wire must be connected firmly and cannot be connected to the neutral wire of the inverter and the safety lightning protection ground wire of the components. At the same time, otherwise it will affect the accuracy of detection and cause the inverter to judge errors.