How to make PLC communicate with inverter through analog quantity?
First open the smart programming software, and then perform hard configuration, select ST3O.
Since our actual PLC is ST30, it must be consistent with the actual one. Then choose the expansion module, there is only one here, we choose AM03.
After is selected, then set the analog output of the module. This (2Ai/1AQ) is two analog inputs and two analog outputs. Today I only set the analog output.
You can choose either voltage or current in this place, depending on your actual situation. We are now connected to voltage. Choose the voltage for this place. This range is plus or minus 10V, plus or minus 10V includes 0~10V, and the others don’t need to be changed. Then click to confirm, and the hardware configuration is complete.
Next, I will start writing programs. Here is a very important thing. You must master the analog conversion library.
After opening the analog library, select the bottom RTI, and then write a direct call SMO.O here. What does this mean? Next, I will introduce to you at each tube angle.
The first input is the input terminal, which is the frequency you want. For example, if you want 50 Hz, you can write 50 Hz, then you say I want it to be between 0-25, any number can be Change, then you write a VD0 address, write a memory, ISH represents the maximum value of the frequency you want, our maximum value is 50.0, which is 50 Hz, ISL represents the minimum value of the frequency you want, that is 0.0.
What do the following OSH and OSL mean? They respectively represent the maximum and minimum values of our analog output.
I will write you 27648 directly, that is to say, your 0-10V voltage signal, then the corresponding PLC is 0-27648, the minimum value is 0, the maximum limit is 27648, which just corresponds to our frequency is 0- 50 Hz, then this place is the output is the output, the output is the analog quantity, the value of the analog quantity is between 0-27648, a variable value, where is it stored? Store it in the place just shown in the picture.
Everyone sees that the channel address is AQW16, that is, you have to fill in this address. The other fills in are wrong. You must fill in this. Write AQW16 in this place. You can see this value from here. It depends on your frequency. Change and change, its change range is between 0-27648. After we write the program, we download it to the PLC.
Precautions:
1. After downloading the program to the PLC, do not click to run.
2. Remember to set the parameters of the inverter.