Typical load characteristics, how to match the frequency converter of the motor more reasonably?
Different load characteristics determine the dynamic changes of motor performance parameters. Different working conditions may cause changes in the torque, current or speed of the motor. All these changes must be considered as factors when selecting the inverter.
Compressors, vibrators and other equipment belong to torque fluctuation load conditions, while hydraulic pump equipment has peak load loads. These are typical variable loads. If the inverter is matched according to the rated current or output value of the motor, Unexpected phenomena such as the overcurrent protection action due to the peak current may occur. Therefore, the inverter with a rated output current greater than its maximum current should be selected to ensure the normal operation of the equipment.
Roots blower is a volumetric blower with the characteristics of high output air pressure. It is mostly used in exhaust tanks of sewage treatment plants. During operation, the output pressure of the pump is basically constant, and the output air volume changes in proportion to the speed. For the motor itself, its torque characteristic is basically a constant torque. However, when the air volume increases, the pressure loss of the piping and the pressure loss of the part where the air blows out of the water increases. About 20% of the pressure loss is related to the rotation speed, which is not constant. When selecting the rated capacity of the frequency converter, it should be 20% larger than the rated value of the motor, and the speed adjustment should be performed above 20% of the rated speed.
The motors in deep well water pumps have special structures. Compared with the same general-purpose motors, the rated current is larger. The selected capacity should be within the rated current of the inverter. In addition, the cooling of the motor is carried out by the flowing water of the pump. Therefore, a certain flow is required. Pumps with high heads such as deep well pumps have a correspondingly high rotation speed. The lower limit should be set according to the rotation speed of the pump.
The centrifuge has a large moment of inertia and requires a large acceleration torque. Moreover, the acceleration time is long, requiring several minutes. Therefore, in order to prevent the overload protection of the inverter during acceleration, the current of the motor should be selected to be below the rated current of the inverter when the inverter is accelerating. In addition, in order to stop quickly, a large deceleration torque is required, and the braking resistor will not overheat due to the increase in the regenerative voltage during deceleration.