What is a soft starter? The role of soft starters
Three-phase asynchronous motors have many advantages, but there are also two fatal weaknesses: one is poor starting performance; the other is poor speed regulation performance. With the development of power semiconductor technology and the application of high-power transistors in the field of industrial control, two typical products have greatly improved the two weaknesses of asynchronous motors, one is the frequency converter, and the other is the soft starter. The frequency converter improves the speed regulation performance of the asynchronous motor; and the soft starter improves the starting performance of the asynchronous motor. In the previous article, a question-and-answer form briefly introduced the relevant knowledge of the inverter. This article will share with you the relevant basic knowledge of the soft starter.
The soft starter has multiple functions such as soft start, soft stop, pump control function, timing and low-speed operation, so it has the incomparable superiority of the traditional step-down starter in the control of power equipment in the industrial and civil construction fields. The characteristics and precautions of the soft starter are as follows:
1. Features
(1) Soft start During the starting time ts, the terminal voltage of the motor gradually increases from the set initial value to the full voltage, and the motor accelerates smoothly and steplessly. At the same time, ts can be adjusted (usually between 0.5 and 60s), which is conducive to coordination with the low-voltage circuit breaker and prevents the instantaneous release of the low-voltage circuit breaker from accidentally tripping when the motor starts.
(2) Pump control function When the pump starts and stops, the water flow hits the pipeline, causing serious water hammer effect. Although the waterway profession has taken some measures to eliminate the water hammer effect, if a soft starter with pump control function is used, the water hammer effect can be completely eliminated, the workload of mechanical maintenance is reduced, the system maintenance cost is saved, and the water supply is reliable. . It is worth mentioning that this function is optional and can be marked on the delivery drawing.
(3) Overload protection function Generally, the overload protection of the motor is realized by the thermal element. It is difficult for the thermal element to avoid the starting current of the motor and cause malfunction during the motor starting process. In order to avoid misoperation, users often increase the operating current of the thermal element, which makes the sensitivity of the overload protection insufficient and makes the overload protection useless. The built-in overload protection function of the soft starter selects different tripping characteristic curves according to the starting load (that is, the length of the starting time) to avoid accidental tripping during the starting process. Because its overload protection is programmable, it provides users with greater flexibility. Choosing the soft starter with built-in overload protection function can also save the thermal relay, making the wiring in the control cabinet easier.
(4) The parameter test function can select and display the operating parameters of the motor in the display window by pressing the button, such as three-phase voltage value, three-phase current value, power factor, running time, etc., without the need to add any instrument, this function can make users very convenient Query various parameters of the motor during operation.
(5) Regular automatic test of fire-fighting water pumps Because fire-fighting water pumps are fire emergency facilities, they are prone to pump jams if they are not used for a long time. Once a fire occurs, if it fails to operate normally, it will affect the smooth progress of fire fighting and cause serious consequences. The "Code for Electrical Design of Civil Buildings" stipulates that important fire-fighting electrical equipment such as fire-fighting pumps (including spray pumps), exhaust fans, and positive pressure blowers should take regular automatic testing and automatic testing measures. The soft starter has the function of timing low-speed operation, and can start and stop automatically according to the time set by the user. It plays the role of regular automatic test and automatic detection of fire pumps, and improves the reliability and emergency of fire protection facilities.
(6) Principle and wiring The soft starter uses three-phase parallel thyristor as a voltage regulator, which is connected between the power supply and the motor stator (see Figure 1 for the specific wiring diagram). When the soft starter is used to start the motor, the output voltage of the thyristor gradually increases, and the motor gradually accelerates until the thyristor is fully turned on. The motor works on the mechanical characteristics of the rated voltage to achieve smooth starting, reduce the starting current, and avoid starting over-current tripping. When the motor reaches the rated speed, the start-up process ends.
2. Issues that should be paid attention to
(1) Some soft starters have a variety of built-in protection functions, such as stall and locked-rotor testing, phase balance, underload protection, undervoltage protection, overvoltage protection, etc., which provide further protection for the motor. When designing, the protection function should be selected or invalidated by programming according to the specific situation. The "Code for Design of Low-Voltage Power Distribution" stipulates that for lines where sudden power failure causes greater losses than overloading, the overload protection should act on the signal and not on the cut-off circuit. For the fire pump control system, the protection of the fire pump motor is not an important issue. Some protection functions can be disabled through programming and only act on the signal. The aforementioned overload protection function should also only act on the signal.
(2) Since the soft starter itself does not have short-circuit protection, in order to protect the thyristor, a fast fuse should be used (low-voltage circuit breakers have a longer breaking time of 0.1s, which cannot effectively protect the thyristor). When designing, you can select the corresponding fast fuse according to the product sample provided by the manufacturer and the rated current of the soft starter.
(3) When the soft starter brakes the motor to stop, only the thyristor does not conduct, and there is no electrical isolation between the motor and the power supply. It is not safe to repair the circuit and motor behind the soft starter at this time, so a circuit breaker should be added before the soft starter in the primary control circuit of the motor.
(4) Since the soft starter uses non-linear devices such as thyristors, when the power of the soft starter is large or the number of units is large, the generated high-order harmonics will have a negative impact on the power grid and affect the electronic equipment in the building. Produce interference. At this time, a bypass contactor can be installed (see Figure 2). After the soft starter starts the motor smoothly to the normal speed, the contactor K is closed and the soft starter is short-circuited. That is, after the start is completed, the high-power thyristor is in a non-conducting state, reducing the interference of high-order harmonics to the power grid and electronic equipment.
(5) The soft starter will dissipate heat when passing current. When installing, pay attention to leaving a certain space above and below it so that air can flow through its power module. When the rated current of the soft starter is large, the fan should be used for cooling. The power supply of the fan can be taken from the secondary circuit of the motor control system.
As explained above, the soft starter is a new type of starting device with excellent performance, and it is currently the first choice for AC asynchronous motor starters.