Details
Features of MIC-600 online phosphine detection alarm:
●Intrinsically safe circuit design, explosion-proof certification, secondary lightning protection, anti-static, lightning protection and anti-static capabilities exceeding national standards, resistance to high-intensity pulse surge current impact. High reliability and stability.
Anti-reverse design, any form of reverse connection will not damage the instrument
●It complies with EMI and EMC standards, and has passed national standard testing and CMC measurement instrument license certification.
Executive standard: GB15322.1-2003
GB 3836.1—2010 "General Requirements for Electrical Equipment for Explosive Gas Atmospheres"
GB 3836.2—2010 "Electrical Equipment for Explosive Gas Environment Explosion-proof Type "d""
GB 3836.4—2010 "Electrical Equipment for Explosive Gas Environment Intrinsically Safe "i""
●Standard bus RS485 (RTU) and 4-20mA standard signal output at the same time, 3 groups of relay switch output, on-site sound and light alarm. Optional frequency output 200-1000Hz, Hart protocol signal, 1~5V output, wireless transmission (2~5km or unlimited distance). Wired or wireless remote real-time monitoring can be performed. Data can be uploaded to a phone or transmitted to the Environmental Protection Agency, other monitoring centers, monitoring equipment, and monitoring computers via a local area network or the Internet. The concentration of the site can be monitored in real time through free upper computer software or gas alarm controllers.
●Compatible with various secondary meters, data acquisition modules, PLC, DCS systems, can directly drive solenoid valves, fans, alarms and other equipment, and can also drive high-power equipment by driving intermediate relays. Optional MIC2000 controller can monitor 1000 detectors at the same time.
●Large-capacity data storage function, can record real-time concentration value, temperature and humidity, or only alarm value and time. Support local storage or SD card storage. The standard storage capacity of this machine is 100,000 records. If a larger capacity is required, please indicate when ordering. SD card storage capacity can be customized. Data export and analysis are carried out through the free upper computer software, and data can be viewed or deleted on the machine. It can be set to automatically overwrite data or not to overwrite data when the capacity is insufficient, and automatically stop recording.
●The standard infrared remote control can realize the operation without opening the cover in dangerous situations, such as: modify the alarm point, concentration calibration, zero point calibration, silence, restore the factory, enter the menu, view the record, 4mA output, 20mA output (calibrate other acquisition equipment) This function is required).
●Chinese and English interface can be selected, the default Chinese interface, support free switching of gas concentration units, conventional gas does not need to enter the molecular weight, and the molecular weight of special gas is automatically calculated and switched after entering the molecular weight. The units are optional: PPM, mg/m3, Vol%, LEL% , PPHM, ppb, mg/L
●The 2.5-inch high-definition color screen (LCM) displays real-time concentration, time, temperature, humidity, storage status and other information. It can detect 1 to 6 gas concentrations and temperature and humidity at the same time. The menu interface uses high-definition simulation icons.