Welcome Customer !

Membership

Wuhan Huatian Electric Power Automation CO., LTD
Free Member ·1YRS
,
Other

Main Products: 电力试验设备

Xwboo>Products

HTXZ(L) Power Frequency Series Resonant Test System

Model
Nature of the Manufacturer
Other
Product Category
one、High voltage insulation
Place of Origin
City, Province
Overview
The output voltage waveform distortion rate (THD) is superior to all existing ac withstand voltage devices Effectively prevent flashover or breakdown, and automatically extinguish arc after flashover Power frequency withstand voltage tester host large output capacity, small power supply required
Product Details

Product Introduction

With the development of power system, the capacity of running equipment is increasing. For example, Thermal generator group, the single capacity has exceeded 1000MW, and hydrodynamo group, the maximum capacity has reached 800MW. If traditional test equipment (power frequency test transformer) is used for the ac power frequency withstand Voltage test of these devices, the regulator is very bulky because of the large test capacity required, and the high-capacity test power supply is difficult to solve in the field, so the field test is extremely inconvenient. The Power frequency withstand voltage tester host, no matter from test Power supply capacity, equipment weight, the waveform and has advantages in such aspects as investment. The Power frequency withstand voltage tester host focuses on the potential of capacity of 250 mw and below hydrodynamo ac withstand voltage test of the design and manufacture.

product names:Power frequency resonance、Power frequency series resonance、Series resonance、Series resonant transformer、Series resonance test equipment、Adjustable frequency resonant voltage withstand device、Power frequency withstand voltage tester host

Product Parameters

Technical parameters

Rated output voltage0 ~ 60kV(AC RMS) and below
output frequency50Hz
Resonance voltage waveformPure sine wave, waveform distortion rate ≤1%
Work systemFull power conticontrol consolenuous working time of 1min
quality factor10~40
Maximum test capacity3000kVA and below
Working power supply380V±15%、Power frequency 50Hz

Serial product configuration(Scope of application(Ac withstand voltage test for generator or motor with outlet voltage of 20kV or below, test frequency: 50Hz))

Product model control console Voltage regulator reactor(dry) Excitation transformer(dry) Voltage divider Scope of application
HTXZ(L)- 200kVA/25kV 30kW 30kVA(electric) 200kVA/25kV Adjustable one 30kVA dry 30kV hydrodynamo.0.4~1.0μF.(10kV/40MW)
HTXZ(L)- 300kVA/50kV 60kW 60kVA(electric) 300kVA/50kV Adjustable one 60kVA oil-immersed 50kV Thermal generator.0.27~0.33μF.(20kV/300MW)
HTXZ(L)- 600kVA/50kV 60kW 60kVA(electric) 200kVA/50kV Adjustable one
400kVA/50kV Adjustable one
60kVA oil-immersed 50kV Thermal generator.0.113~0.45μF.(20kV/600MW)
HTXZ(L)- 1200kVA/50kV 120kW 120kVA(induction) 200kVA/50kV Fixed two
800kVA/50kV Adjustable one
120kVA oil-immersed 50kV hydrodynamo.0.6~1.8μF.(20kV/250MW)
HTXZ(L)- 2750kVA/55kV 300kW 300kVA(induction) 750kVA/55kV Fixed two
1250kVA/55kV Adjustable one
120kVA oil-immersed 60kV hydrodynamo.1.6~3.3μF.(20kV/770MW)

Note: the solution can be customized according to the parameters of test objects

Capacitance of the power system commonly used hydrodynamo reference table

hydrodynamo Rated Capacity(WM) rated voltage(kV) Phase capacitor(μF)
72.5~85 10.5 0.694
125~150 / 1.8~1.9
300 15.75 1.7~2.5
400 18.0 2~2.5
600 / 2.1~2.5
Note:

1.The appearance of the product shall be subject to the actual product,Technical parameters with model if there are any changes,without notice.In case of misappropriation or copying, legal liability will be investigated.

2. For more information about huatian products, please enter product center .Service :qiao@hvtest.cc

Product Characteristics

  • 1、Due to full compensation of resonant reactive power, the power of power supply and equipment is less than 1/10 of the required capacity of the subject (1/q10); Small size and light weight with the same capacity, large output capacity of the device and small power capacity required for configuration, cheap, convenient and safe operation.

  • 2、Series resonance is actually a current filtering circuit, so that the current passing through the subject is basically the fundamental current, and the waveform distortion rate (THD) of the output voltage is very small, which is superior to all existing ac voltage withstand equipment.

  • 3、The short circuit current of the sample after flashover or breakdown is only less than 1/10 (1/Q) of the test current before short circuit, which can effectively prevent the expansion of damage to the fault point after breakdown.

  • 4、After flashover, the arc will be automatically extinguished immediately. The long (number of seconds) process of restoring resonant state voltage after arc quenching is a steady-state establishment process, and there is no danger of voltage overshoot and no danger of restoring overvoltage in microsecond millisecond transient process.

Product Video