For voltage from 6kV to 35kV overhead lines detection Measuring range: ground resistance≤100kΩDetect line length: ≤100kmGround Impedance Measurement: 0~2000 kΩOutput AC detection current: 0~40±2mAOutput AC detection voltage: 0~3kVOutput DC ground impedance current: 0~37±2mAOutput DC ground impedance voltage: 0~4.2kVOutput Power: Effective maximum output power 95W
Product Details
XHJK531A overhead line fault locator is an inspection device for single-phase grounding fault points of distribution lines, which is used to find single-phase grounding fault points of 6kV, 10kV, 20kV, and 35kV overhead lines. For concealed ground faults such as breakdown of porcelain bottles and breakdown of arresters, this device can save time and effort, and can shorten the search time by 60%.
When the line has a ground fault, in the state of cold standby of the line (without any grounding protection when the power is cut off), a detection signal with a certain power is injected into the line through the signal generating device (referred to as: signal source), and then the hand-held data detection device (referred to as the signal source) is injected into the line. : clamp meter) measure the signal current on both sides of the injection point, and judge the difference between the fault side and the fault through the data displayed by the hand-held data receiving device (referred to as: hand copy device).
Keep the injection point of the signal source not moving. On the fault side, use the dichotomy method to measure the current at half of the faulty line to further determine the faulty section, and so on to reduce the faulty section by half each time until the fault point is found.
The principle of using the locating device to find the ground fault is shown in the following figure:
Using the equipment can quickly and accurately find the fault point, and the fault point error does not exceed 1 meter. It is convenient to carry and use. The signal source is powered by lithium battery, which is small in size and light in weight.
The operator operates through an insulating rod, and there is an overvoltage protection inside the device to ensure safe operation.
Equipment composition
The device consists of a signal injection part and a signal detection part.
Signal injection part
The function of the signal injection part is to inject a 22Hz detection signal into the ground fault line when the line is powered off. Main components: signal source. Accessories: signal output wire, ground wire, retractable gram bars (3 pieces), single-tongue grounding hooks (3 pieces), charger, etc., as shown in the figure below.
Signal detection part
The main components of the signal detection part: clamp meter, hand copy device, as shown in the figure below. Accessories: retractable gram stick (1 piece).
1) Clamp meter, used to measure the detection signal from the signal source.
2) Hand copy device, used to receive and display the measurement data sent back by the clamp meter, and can perform operations such as data retention, storage, review, deletion, etc.
Positioning device carrying case
Except for the signal source, all accessories of the positioning device are placed in the carrying bag, as shown in the figure below.
Technical Parameters
★Signal Source Specifications
Output AC detection current
0~40±2mA
Output AC detection voltage
0~3kV
Output DC ground impedance current
0~37±2mA
Output DC ground impedance voltage
0~4.2kV
Ground Impedance Current Accuracy
±1mA
AC detection signal output accuracy
±1mA
Output Power
Effective maximum output power 95W
Measuring range
ground resistance≤100kΩ
Detect line length
≤100km
Ground Impedance Measurement
0~2000 kΩ
Ground impedance measurement accuracy
10%±2kΩ
Signal loop open circuit protection time
≤1S
Signal output loop integrity detection protection time
≤2S
Detection signal fluctuation alarm threshold
±2mA
Open Circuit Identification Current Threshold
≤2mA
Low power alarm
23V
Under voltage power outage
22V
No operation automatic power off time
0~10S
Display mode
Dot matrix display, backlight function
Rated working voltage
24VDC
Operating voltage range
21-29.4V
Battery capacity
24V/7AH
Battery voltage detection accuracy
2%
Power maintenance time
>3.5小时
Working temperature
-20℃~50℃
Size(mm)
L457*W370*H184
Weight
11.3Kg
★Specifications of Clamp Meters and Hand Copiers
Detection method
Clamp CT, integral method
Transfer method
433MHz wireless RF transmission, the transmission distance is about 30m
LCD size
62mm×44mm
Device size
Length100mm×Thickness35mm×Height204mm
Jaw size
Ф50mm
Measuring range
0.1mA~1200A(50Hz)
0.1 mA~200 mA(22Hz)
Sampling frequency
2 times/sec
Resolution
0.1mA
Test accuracy
±2%±5dgt (23℃±5℃,below80%RH)
Data storage
99 groups, the "MEM" symbol indicates during the storage process, and the "FULL" symbol flashes to indicate that the storage is full
Line voltage
The line is charged not more than 35kV (operated with insulating rod)
Data retention
In detection mode, press the HOLD key to hold the data, the "HOLD" symbol will be displayed, and then press the HOLD key to cancel the hold
Data access
"MR" symbol indicates that the stored data can be paged up and down
Over-range overflow display
"OL A" symbol display
No signal indication
Dynamically display the "no- -" symbol when the hand copy device does not receive the transmitted signal
Automatic shut-down
If not detected, the device will automatically shut down after about 15 minutes
power supply
DC6V 4 AA alkaline batteries, wireless reception: 5 1.5V AA alkaline batteries
Battery voltage
When the battery voltage is lower than 5.4V, the low battery voltage symbol will be displayed to remind you to replace the battery
Device weight
The total weight of clamp meter and hand copy machine is 2.5Kg (including insulating rod and battery)
Working environment temperature and humidity
-10℃~40℃; below 80%Rh
Storage environment temperature and humidity
-10℃~60℃; below 70%Rh
Interfere
No interference from 433MHz co-channel signals
Insulation rod size
Telescopic insulating rod 4 meters/section (4 sections)
Dielectric strength
AC 40kV/rms (Between the insulating rod and the clamp core)
Structure
Anti-drip type II
How to use the XHJK531A overhead line fault locator to find the ground fault point?
●Preparations
1) Before starting work, make sure that the faulty line is in a power-off state and is not grounded.
2) Make sure that the components of the positioning device are complete and the power is sufficient.
3) What to bring: a set of positioning devices (see the packing list); a pair of foot buckles; a pair of insulating shoes; a pair of insulating gloves; a test pen; a number of safety helmets (depending on the number of people); A record book; a fault circuit diagram.
●Security Detection
Figure 1
As shown in Figure 1: Before using the equipment, please first perform the circuit electrical inspection operation. The equipment is strictly prohibited to be used under live conditions to prevent equipment damage and electric shock to equipment operators.
●Grounding Field Equipment Assembly and Commissioning
The first step is to prepare the signal injection part
Figure 2
As shown in Figure 2: After arriving at the site, in the state of cold standby (the entire line cannot be grounded), clamp the other end of the grounding wire to the tower grounding wire or grounding drill, and ensure that the grounding is good.
Figure 3
As shown in Figure 3: Connect the other end of the ground wire to the ground socket of the signal source, and rotate to lock it.
Figure 4
As shown in Figure 4: Connect one end of the red signal output wire to the signal output socket of the signal source, and rotate to lock it.
Figure 5
As shown in Figure 5: Hook the 3 hook terminals at the other end of the signal output line to the fixing bolts of the 3 single tongue hooks in turn, and use the wing nuts to lock them.
Figure 6
As shown in the figure6: The signal output line is installed as shown in the figure.
Figure 7
As shown in the figure7: Hang the three hook insulation rods connecting the signal output lines to the three-phase wires of the faulty line respectively.
The second step is to debug the clamp meter and the hand copy device
Connect the hand-held signal detection device (abbreviation: clamp meter) to the insulating rod. Press the POWER button of the clamp meter to turn on the power, and the power indicator light is on.
As shown in the figure: Press the POWER button of the handheld data receiving device (abbreviation: hand copy device) to turn on the power. At this time, if the screen displays 0.0mA, and the upper right corner of the screen displays 22Hz, it means the communication is normal. If it displays 50Hz, you can press " 22Hz/50Hz" button to switch the frequency.
The third step is ground Impedance Measurement
Figure 8
As shown in Figure 8: Turn on the power switch of the signal source, the power indicator is on, and the LCD is in the standby interface.
(1)In the standby interface, press the "output key", the device enters the function selection interface
(2)In the function selection interface, use the "Stop" key to select the grounding impedance measurement function, and use the "Output key" to enter the grounding impedance measurement interface
(3)Ground impedance is measured by injecting a high voltage DC signal into the line.
The fourth step is AC detection signal injection
In the function selection interface, select the output detection signal function through the "stop key", and enter the detection signal output interface through the "output key".
Under the detection signal output interface, the device injects the detection signal into the line, and displays the current, voltage and frequency difference of the detection signal.
●The method of judging the grounding section and the grounding phase
1) Use the grounding impedance measurement function to confirm whether the line has grounding and grounding impedance.
2) Measure the current values on both sides of the A, B, and C three-phase signal injection points respectively, and mark them on the corresponding positions of the circuit drawings.
3) Judging the grounding section and the grounding phase: compare the difference between the three-phase currents on both sides of the injection point. If the three-phase current on one side is unbalanced (the difference is greater than 2mA), it is the fault side, and the fault side signal detects the larger current value. The phases are the faulty phases.
●Find the grounding point method
1) Keep the signal injection point of the signal source not moving;
2) Use the dichotomy method to detect the three-phase currents of A, B, and C respectively at the midpoint or large branch of the determined fault side and mark them on the corresponding positions of the circuit drawings. If the three-phase currents are unbalanced (the difference is greater than 2mA), The ground point is on the side away from the signal source, and vice versa, on the side close to the signal source;
3) In the newly determined grounding interval, continue to search according to the method of 2) until the grounding point is found.
Common question
1. Can all ground faults be found by using the XHJK531A overhead line fault locator?
In theory, all permanent earth faults can be detected by the locating device. In practice, there are sometimes exceptions:
(1) After the substation ground fault is alarmed, the positioning device cannot be used to find it. This kind of ground fault is transient (for example, the substation alarm is caused by the short-term overlapping of branches), or it is intermittent (there is a crack inside the porcelain bottle, and the rainwater flows through the crack to cause a ground fault, and the substation alarms, and when the fault is found, the rainwater has dried up. dry, the ground channel disappears).
(2) The positioning device finds that there is no fault, but the ground fault occurs when the power is tested. This situation is because the grounding resistance is large, which can break down under the system voltage, causing the substation grounding fault alarm. The maximum applied voltage of the signal source is 3000V, which may not be able to break down for high resistance or intermittent faults, resulting in the illusion of no ground fault. In this case, first test the power transmission, the ground fault will recur during the test power transmission, and then use the positioning device to find the power failure. Because the grounding resistance will decrease rapidly under the repeated breakdown of the system voltage, the fault point can be found smoothly at this time.
(3) For grounding faults with large grounding resistance, the method of segmented detection can be used. Disconnect the line segment switch to divide the line into 2-3 segments and detect them separately, which can significantly increase the success rate of finding faults.
If you encounter difficulties in finding, please call our company's technical service telephone at .
2. Compared with insulation shaker testing, what are the advantages?
To use the insulation shaker to detect and find faults, it is necessary to divide the line into several sections according to the detection situation. When dividing, it is necessary to disconnect the switch, wire tool, or remove the bridge wire. And in order to avoid the influence of distribution transformers, all distribution transformers need to be disconnected. This process is very labor-intensive and time-consuming, with a large amount of engineering, and the exact point of failure cannot be determined. The positioning device does not need to segment the line or disconnect the distribution transformer. Using the "dichotomy" principle, after several searches, the fault point can be determined at a certain equipment on a certain level of poles, and the efficiency of search is higher than that of shaking. Table detection is much higher.
3. How does it compare with other similar products?
At present, the company's positioning device is the only product in the industry that is powered by batteries and does not require an external power source or generator during operation. Moreover, the volume and weight are only half of those of similar products, making it easy to carry and especially suitable for troubleshooting in areas that vehicles cannot reach.
4. Can the fault of the insulated wire be checked?
The positioning device can be used to find the ground fault point of the insulated wire. When the signal is injected, the insulating rod connecting the signal output wire can be hooked to the grounding ring of the wire. Other operations are the same as bare wires.
5. Why use the dichotomy and where to start?
The dichotomy method is one of the fastest ways to find the fault point. It is recommended to inject the signal from the middle of the line first, which can immediately reduce the fault range by half. The injection point location can also be chosen empirically.
6. What should I pay attention to when searching?
When testing data and making judgments, you need to pay attention not to confuse the large side and the small side of the line. Due to the long line, the three-phase wires may be commutated. Be careful not to confuse the three-phase wires.
7. Why is segmentation sometimes necessary?
In the case of large grounding resistance, the distributed capacitance of the line will affect the detection result, which may lead to inability to judge or wrong judgment. Segmenting the line can effectively reduce the influence of the distributed capacitance of the line and improve the success rate of fault finding.
8. Can the ground fault of the cable line be detected?
Yes, the cable line detects the ground fault. It is necessary to inject signals at the bare line of the line or the internal joint of the ring network cabinet to detect the three-phase signal current of each branch cable. If the three-phase current of the cable is unbalanced, the cable fault can be judged; At the other end of the faulty cable, if the three phases are unbalanced, it is judged that the rear end of the branch line is faulty.
9. What should I do if the two-phase current is large?
The two-phase currents are relatively large, and there may be the following situations:
(1) If the current of the wire drain line is relatively small, a phase failure occurs in one phase. Generally, you can observe or ask the user whether there is an abnormal phase loss;
(2) If the two phases with large current are grounded, the single-phase grounding search method is still used to eliminate them one by one;
(3) The inherent characteristics of the line itself cause the imbalance of three-phase stray parameters, and you can try to transmit power.
10. What should I do if the measurement data fails to determine the fault?
As long as you follow the correct operation steps, accurately measure and record the data, you can theoretically find the grounding point.
If you need technical guidance, you can call our company's technical service phone, and we will provide professional analysis and advice to assist in finding fault points.
Packing List
Name
Qty.(unit)
Host
1
Signal output line
1
Clamp meter
1
Hand copyer
1
Charger
1
Ground wire
1
Telescopic insulating rod
1
Ground hook
1
Remarks
◆This pointing device has passed the international standard certification ISO
◆The general delivery time of the equipment is 8-10 working days. The specific negotiation at the time of ordering shall prevail.
◆The standard packaging is a wooden box for export to protect the safety of equipment transportation.
◆Usually shipped by international express, such as FEDEX, DHL, , ARAMEX, etc. It can be negotiated according to different countries.
◆XZH Team is a young team. Our development philosophy is humanized management, intelligent cloud-based products, and internationalized operations. Our development mission is to make electrical equipment free from undetectable failures.
XZH TEST welcomes your inquiry
FAQ
Q: Are you trading company or manufacturer?
A: We are manufacturer.
Q: What’s your terms of payment?
A: Payment≤USD2000, 99% paid in advance. Amount over USD2000, can be negotiated.
Q: Why should you buy the overhead line fault locator from us?
A: Professional R&D and technical support, accept OEM, ODM orders;
Provide overall laboratory solutions to your project.