Electric Bridge Cable Fault Locator

Model
Nature of the Manufacturer
Manufacturer
Product Category
Power Cable Testing Equipment
Place of Origin
City, Province
Overview
Input voltage: AC 220V (±10%), 60Hz (±2Hz); No-load voltage ≥7500V;Short circuit current ≥ 40mA;Positioning scale accuracy ± (0.2% L ± 1) meters;The output voltage is adjustable;The shock frequency is adjustable;With overcurrent protection;The test range has no blind spot; Signal frequency adjustment;Zero protection.
Product Details

instruction

Electric bridge cable fault locator is designed based on the principle of MURRAY bridge. Compared with the wave reflection method, the bridge balance method has no dead zone, and is especially suitable for judging the breakdown point of short cables and near the end.

 

The device adopts switching power supply to form a high-voltage constant current source, no-load voltage 7500V (can be customized within 10KV), short-circuit current does not exceed 40mA, The equipment has high voltage, light weight, convenient operation and safe use.

 

It can test the breakdown point of various wires and cables after laying and the location of defect points with no breakdown but low insulation resistance value. It is especially suitable for rough measurement of outer sheath faults. Of course, it can also be used to locate the defect points of various cables in the cable factory.

 

The device adopts high-sensitivity amplifier and galvanometer to indicate balance, and forms a balance bridge with proportional potentiometer. The introduced error, the cable is reliably grounded through the braided shielding layer, and when the operation button on the panel is at a low potential, the bridge is operated through the insulating rod. The high voltage constant current source and bridge are integrated in a portable aluminum alloy case.

Electric bridge cable fault locator is especially suitable for

1. The high-resistance breakdown point of the cable after laying, especially the linear high-resistance breakdown point that is difficult to burn low-resistance, such as the linear high-resistance breakdown of the cable intermediate joint.

2. Flashover type breakdown point. After the breakdown, the constant current source can maintain the arc, a stable current flows through the bridge, and the bridge has sufficient sensitivity.

3. The defect points that have not yet broken down but have low resistance, such as the insulation defect points that have low resistance value of the cable but do not break down under the operating voltage are found by using a megohmmeter.

 

Due to the above characteristics, the high-voltage cable outer sheath fault tester is especially suitable for the following users:

 

Teams engaged in professional positioning: such as cable repair and trial classes for large and medium-sized power supply bureaus and large-scale electricity enterprises. For most of the cable breakdown points, the approximate breakdown location can be quickly found with the cable jacket fault tester. It can be used in conjunction with the wave reflection method and the fixed point meter to learn from each other's strengths and make the positioning faster and more reliable.

 

1. Small users: such as small power supply bureaus and medium-sized electricity enterprises. There are not many cables, the general direction is clear, not too long, and the number of failures is limited. If a set of wave reflection method locator is equipped, the price is high, and the quality and experience of the users are high, so it is not the best choice. It is a better way to choose the XHHG521 tester, which is easy to operate and can meet daily needs.

 

2. Cable production plant: In the factory, it can be used to locate the breakdown point of various cables, and a digital capacitance meter can be selected to find out the disconnection point. The device is light in weight and easy to carry to the field for positioning services for cable users.

 

working principle

The distances from both ends of the cable under test to the breakdown point are L1 and L2, the full length of the cable is L, and their corresponding core resistances are R1, R2

           Obviously, the following circuit is formed after connecting to the bridge

 

The actual wiring is as follows:

 

■HV is a high voltage constant current source,

■The faulty cable CD and the auxiliary cable AB have the same core cross section, the length is L, and the distance from the fault point to the measuring end is X.

■The measuring clip is connected to both ends of the cable cores A and C. The two sides of the clip are the current potential terminals, which should be connected to the cable reliably.

■R is a 10-turn potentiometer for balance, and the dial reading is in thousandths.

■G is a galvanometer, and the zero point of electrical balance is adjustable.

■ Short-circuit both ends of BD through the special short-circuit line of the C-type clip at the far end.

 

Measurement steps:

1. Use a multimeter, shaker or other voltage-resistant equipment to confirm the breakdown state of the cable, and record the insulation resistance to ground or the breakdown residual voltage of each core.

2. Record the length, type, cross-section and other parameters of the cable to be tested, patrol along the cable laying path, short-circuit the faulty cable and auxiliary cable outlet terminals at the remote end, and leave one person to monitor at the remote end to avoid high voltage injury.

3. Wiring. The ground terminal of the instrument is reliably connected to the grounding body of the positioning site. The ground rod is connected to the ground terminal of the instrument. The measuring head (black clip) is connected to the faulty cable core, and the measuring end (red clip) is connected to the auxiliary cable core.

4. Zero adjustment of the bridge (when the high voltage knob is not at the zero position). Turn on the power and turn the zero adjustment knob to make the galvanometer point to zero.

5. The power supply is connected to AC220V.

6. Boost. Turn on the power switch, the power indicator lights up. The high pressure adjustment knob is fully counterclockwise, and the zero position is activated.

7. Slowly rotate the high-voltage adjustment knob clockwise and observe the voltmeter and ammeter until the ammeter exceeds 5mA. If the current is unstable, the voltage can be continuously increased for a period of time to form a stable arc or conductive area, so that the current during the test is stable.

8. Balance adjustment. Turn the zoom knob clockwise to increase the sensitivity step by step until the galvanometer deflects significantly but not excessively. Rotate the ‰ dial to make the galvanometer point to zero. (If the pointer is to the left, rotate clockwise, and if the pointer is to the right, rotate counterclockwise). Write down the reading P1‰ of the ‰ dial at this time.

9. Drop the voltage and discharge. Change the position of the measuring clamp, repeat steps (4) to (10) to get another reading P2, there should be P1+P2=1000

10. Calculate. The position of the fault point X=2×L×P1‰

Special attention should be paid to the "2" in the formula, the auxiliary cable doubles the length of the cable involved in the calculation.

 

Other  matters:

1. Sometimes interference will affect the zero position of the galvanometer, and it can be re-zeroed at the last sensitivity position. The test voltage drops to zero, and the others remain unchanged. Once again boosted, balanced adjustment, the value is more accurate.

2. Use cores with different cross-sections as auxiliary cables, and finally convert them to the length of the faulty cable.

If the fault section is Sx and the auxiliary cable is S, the above formula becomes:

X=P1‰×(1+Sx/S)×L

3. The three-core cables are all broken down or short-circuited with each other, and the core with the best insulation resistance can be selected as the auxiliary cable.

(4) It is helpful for the test to fully understand the factors that affect the sensitivity:

1. The greater the current through the bridge, the higher the sensitivity.

2.The greater the resistance of the cable conductor, the higher the sensitivity, that is, the sensitivity of the thin and long cable is higher, and the sensitivity of the thick and short cable is lower. High amplifier sensitivity.

 

Precautions for use of  instrument & common faults

1.  It is forbidden to touch the high-voltage connecting line and the cable to be tested when using Electric bridge cable fault locator to test, so as to avoid high-voltage injury;

2. Do not turn on the power when the cable is connected, and turn off the power at the end of the test;

3. When the voltage regulation is not at the zero position, the instrument cannot be started;

4. It can only be used when at least two people are present, one is wiring, the other is checking, and the test is started after it is accurate.

5. The grounding terminal of the instrument must be grounded reliably. Use a special grounding wire, preferably clipped on the grounding column of the test site, the grounding bar of the electrical cabinet, and the foot of the mechanical equipment.

6. During the test and after the test, before people touch the high-voltage parts, they must first discharge, and finally hang up the ground wire.

 

on-site case

 

Remarks

◆This pointing device has passed the international standard certification CE  ISO9001

◆The general delivery time of the equipment is 5-8 days. The specific negotiation at the time of ordering shall prevail.

◆The standard packaging is a wooden box for export to protect the safety of equipment transportation.

202208111634052820286a1b874abb969cd932bd7a0aa7

◆Usually shipped by international express, such as FEDEX, DHL, , ARAMEX, etc.

20220811163351f6ac0f9b1126493e9faf0f14

 

◆XZH Team is a young team. Our development philosophy is humanized management, intelligent cloud-based products, and internationalized operations. Our development mission is to make electrical equipment free from undetectable failures.

202208111634389f28bc3b788947d8924be9818a4e6ac4

 

XZH TEST   Welcome your inquiry~

 

FAQ

Q: Would you accept OEM order?

A: Yes, we accept, welcome you contact us for more discussion.

Q: What’s your terms of payment?

A: Payment terms can be negotiated, in general, Payment≤USD2000, 99% paid in advance.

Amount over USD2000, can be negotiated.

Q: Why should you buy the Electric Bridge Cable Fault Locator  from us?

A: Professional R&D and technical support.

Provide overall laboratory solutions to your project.

Strict quality control and one year of warranty.

Short lead time and fast delivery.